ELECTRICAL CONNECTION
CAUTION: Before working, turn off the electricity at
the main circuit breaker.
- The installation must be carried out in the rules of
the art and meet the standards in force in the country
(NF C 15-100 in France).
- The unit must be connected to a standard wall box
placed at least 25 cm from the floor.
- The appliance must not be connected to an outlet
with a power plug.
- The appliance must be supplied through a residual
current device (RCD) having a rated residual
operating current not exceeding 30 mA.
- The appliance must not be connected to the earth
wire (yellow and green wire).
ELECTRICAL CONNECTION
Blue or light gray wire connect to Neutral (230V)
Brown or red wire connect to Phase (230V)
Black wire connect to pilot wire. (Optional function to
use in case of control by pilot wire box)
WARNING!
(Do not connect the black wire to the
ground).
- In the absence of pilot wire, insulate the bare end
of the black wire to prevent electrical contact with the
other wires or ground.