SAFETY INSTRUCTIONS

c. Before attempting the procedure ensure that:

- Mechanical handling equipment is available, if required, for handling refrigerant

cylinders;

- All personal protective equipment is available and being used correctly;

- The recovery process is supervised at all times by a competent person;

- Recovery equipment and cylinders conform to the appropriate standards.

d. Pump down refrigerant system, if possible.

e. If a vacuum is not possible, make a manifold so that refrigerant can be removed from 

various parts of the system.

f. Make sure that cylinder is situated on the scales before recovery takes place.

g. Start the recovery machine and operate in accordance with instructions.

h. Do not overfill cylinders. (No more than 80 % volume liquid charge).

i. Do not exceed the maximum working pressure of the cylinder, even temporarily.

j. When the cylinders have been filled correctly and the process completed, make sure that 

the cylinders and the equipment are removed from site promptly and all isolation valves

on the equipment are closed off.

k. Recovered refrigerant shall not be charged into another refrigerating system unless it

has been cleaned and checked.

14. Labeling

Equipment shall be labeled stating that it has been de-commissioned and emptied

of refrigerant. The label shall be dated and signed. Ensure that there are labels on the 

equipment stating the equipment contains flammable refrigerant.

15. Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is 

recommended good practice that all refrigerants are removed safely. When transferring 

refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are 

employed. Ensure that the correct number of cylinders for holding the total system charge

is available. All cylinders to be used are designated for the recovered refrigerant and

labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders 

shall be complete with pressure relief valve and associated shutoff valves in good working 

order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery 

occurs. The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery of 

flammable refrigerants. In addition, a set of calibrated weighing scales shall be available 

and in good working order. Hoses shall be complete with leak free disconnect couplings 

and in good condition. Before using the recovery machine, check that it is in satisfactory 

working

order, has been properly maintained and that any associated electrical components are 

sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in 

doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants

in recovery units and especially not in cylinders. If compressors or compressor oils are to be 

removed, ensure that they have been evacuated to an acceptable level to make certain that 

flammable refrigerant does not remain within the lubricant. The evacuation process shall be 

carried out prior to returning the compressor to the suppliers. Only electric heating to the 

compressor body shall be employed to accelerate this process. When oil is drained from a 

40

f

o

28

e

g

a

P

Summary of Contents for OCEADH20L

Page 1: ...Page 1 of 40 REF OCEADH20L Deshumidi cateur d air Guide d utilisation DEHUMIDIFIER User manual...

Page 2: ...eil Le surveillance L appareil doit tre stock de mani re viter tout dommage m canique Ne pas utiliser les eaux r colt es pour les humains ou les animaux domestiques UTILISATION AUTORIS E ATTENTION cet...

Page 3: ...ordon lectrique avant de d placer l appareil AVERTISSEMENTS LECTRIQUES L alimentation lectrique doit tre de tension nominale avec un circuit sp cial pour l appareil Le diam tre du c ble lectrique doit...

Page 4: ...e europ enne 2012 19 UE relative aux d chets d quipements lectriques et lectroniques DEEE En s assurant que ce produit est correctement mis au rebut vous contribuerez emp cher toute cons quence nuisib...

Page 5: ...mati re de transport 2 Le marquage de l quipement par le biais de signalisations doit tre conforme aux r glementations locales conforme aux r glementations nationales 4 Le stockage de l quipement des...

Page 6: ...ment a r e avant de rentrer dans le syst me ou de r aliser des travaux chaud Un certain degr de ventilation doit tre maintenu pendant la p riode de r alisation des travaux La ventilation doit permettr...

Page 7: ...orrecte des presse toupes etc Il convient de s assurer que l appareil est mont en toute s curit Assurez vous que les joints ou mat riaux d tanch it ne sont pas d t rior s au point de ne plus pouvoir s...

Page 8: ...e pour faire des r parations ou pour tout autre but des proc dures conventionnelles doivent tre utilis es Toutefois il est Il convient de suivre la proc dure suivante Enlevez le r frig rant Purgez le...

Page 9: ...e protection individuelle est disponible et utilis correctement Le processus de r cup ration est supervis tout moment par une personne comp tente L quipement de r cup ration et les cylindres sont conf...

Page 10: ...u fournisseur de r frig rant dans le cylindre de r cup ration correct et la Note de Transfert de Rebut pertinente doit tre pr par e Ne m langez pas les r frig rants dans les unit s de r cup ration et...

Page 11: ...umidi cateur sur un tapis ou sur des objets Le cas ch ant de l eau pourrait s couler du bac de r cup ration ou le d shumidi ateur se coincer sur les objets 12 Ne d placez pas l appareil sur ses roulet...

Page 12: ...roduit 1 Panneau de commande num rique 2 Poign e 3 Entr e d air 4 Sortie d air 5 Bac de r cup ration d eau 6 7 Roulettes 8 Raccord de tuyau de vidange continue 9 Filtre 10 Voyant d humidit 1 2 10 7 40...

Page 13: ...eur 17 TOUCHE MINUTERIE R gler la minuterie pour allumer ou teindre l unit de 01 24 heures 18 TOUCHE S CURIT ENFANTS Enfoncer pour verrouiller ou d verrouiller le bouton 19 Voyant s curit enfant 20 Vo...

Page 14: ...ant cont 29 s allume l appareil fonctionne en mode cont R gle automatiquement la vitesse basse du ventilateur et le ateur fonctionne en continu Le niveau d humidit r gl est d sactiv Mode Fort lorsque...

Page 15: ...te actuelle et le voyant r s 5 sec temp rature LED indique nouveau automatiquement l humidit ambiante MINUTERIE DESCRIPTIONS DES FONCTIONS FONCTION S CURIT ENFANT Enfoncez la touche S CURIT ENFANT 18...

Page 16: ...cup ration car ils pourraient et p l endommager rovoquerdes fuites d eau 2 Vidange de l eau Si le bac de r cup ration d eau est extrait pendant le fonctionnement ou imm diatement apr s avoir teint la...

Page 17: ...guli re ou si le tuyau est mal install l eau risque de remplir le bac de r cup ration et de provoquer l arr t de l unit Le cas ch ant videz le bac de r cup ration d eau puis v rifiez l emplacement du...

Page 18: ...er l unit par intermittence et nettoyez le sol en dessous NETTOYAGE DU FILTRE AIR Si le filtre est obstru par de la poussi re le d bit d air et les performances de l unit en seront affect s Contr lez...

Page 19: ...V r vous avez r gl la fonction minuterie Attendez 3 minutes puis red marrez l appareil il se peut que le dispositif de protection emp che le fonctionnement La vitesse du ventilateur ne peut tre r gl e...

Page 20: ...mod le exac ateur le num ro de service c est le num ro que l on trouve sous le mot Service sur l autocollant de service situ sur le c t ou au bas de l unit votre num ro de t l phone Si des travaux de...

Page 21: ...erning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision...

Page 22: ...losion or fire Operate the appliance only on a level and stable surf ace Disconnect power cord before moving the appliance ELECTRICAL WARNINGS The power supply must be of rated voltage with special ci...

Page 23: ...suring this product is disposed of correctly you will help prevent negative consequences for the environment and human health The symbol on the product or on the accompanying documentation indicates t...

Page 24: ...hall be compliant with local regulations Regulations 4 The storage of equipment appliances should be in accordance with the manufacturer s instructions 5 Storage of packed unsold equipment Storage pac...

Page 25: ...d If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants The actual refrigerant charge is in acc...

Page 26: ...esence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts may result in the ignition of refrigeran...

Page 27: ...for the vacuum pump is not close to any potential ignition sources and there is the vacuum in the system with OFN and continuing ventilation available 12 Charging procedures In addition to convention...

Page 28: ...ylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge is available All cylinders to be used...

Page 29: ...e unit might get them wet and may cause damage or malfunction of your property To keep ventilation openings clear of obstruction The appliance shall be stored in a well ventilated area where the room...

Page 30: ...tes it should be kept at least 50 cm from any object to prevent dripping from causing malfunctions or potential fire hazards 11 The dehumidifier has rollers to aid its positioning Do not attempt to ro...

Page 31: ...ion 1 Control Panel and Digital 2 Handle 3 Air Inlet 4 Air Outlet 5 Water Bucket 6 Water Level Display 7 Castor Wheels 8 Continuous Draining Hose Connection 9 Filter 10 Humidity Indicator Light 1 2 10...

Page 32: ...MER BUTTON Set the timer to turn the unit on or o between 01 24hrs 18 CHILD LOCK BUTTON Press to lock or unlock the button 19 Child Lock Indictor 20 Full bucket indicator 21 Defrost Indicator 22 Sleep...

Page 33: ...ppliance operates in Cont mode Automatically sets the fan low speed and the continuously Set humidity level is unable Strong Mode when the Strong indicator 27 lights up the appliance operates in Stron...

Page 34: ...ETTING button 13 for 5 seconds LED display can show the current ambient temperature and the indicator 28 in the LED display lights up After 5 seconds of temperature display LED display automatically r...

Page 35: ...to clean the bucket as these may damage it and cause water leakages 2 Draining the water If the water bucket is extracted during operation or immediately after turning off the machine water may drip o...

Page 36: ...r they are damaged or blocked Placing the appliance on an uneven surface or improper hose installation may lead to water filling the bucket causing the unit to switch off Should this occur empty the w...

Page 37: ...to prevent this from occurring NOTE T ter should be cleaned every two weeks I nt ventilation ma ation performance frost build up and dripping 1 Remove the Air inlet 3 out from the back of the unit 2 R...

Page 38: ...contact Check whether you have set the Timer function Wait 3 minutes then restart the appliance the protection device may be preventing operation The fan speed cannot be adjusted In the Continuous St...

Page 39: ...ce Failure to comply with these instructions could compromise the safety and quality of your product Page 39 of 40 ENVIRONMENTAL PROTECTION This symbol is known as the Crossed out Wheelie Bin Symbol W...

Page 40: ...Page 40 of 40 www oceanic eu...

Reviews: