TO CHECK THE NUMBER OF HOURS ON THE UNIT
1) Disconnect unit power, and reconnect unit power.
2) When “888” appears in display, push and release the arrow down button
3) The first set of numbers dis-
played reads thousands of hours:
02 = 2000, 04 = 4000 hours, 00
means less than 1000 hours.
4) The second set of numbers read hours directly:
58 = 58 hours. 742 = 742 hours.
6) Add the 2 number sets together to get total hours.
03 and 486 = 3486 hours.
01 and 59 = 1059 hours.
TOTAL HOURS REPRESENTS COMPRESSOR “RUN” TIME
MODEL
CODE SETTINGS
OWC2412QC
P1 = 70, P2 = 50
OWC2412QC PROGRAM SETTINGS
NOTICE
Program Parameters are NOT controller default values.
They are Oceanaire Factory Settings
DISPLAY FAULTS
LAC…………………….
Low AC line power
AAA or - - -
………
Failed Air Sensor (unit will not run)
CON…………………….
Failed Condensate Pump/Over-Flow Alarm
High Pressure Cut-Out
—
Low/interrupted condenser
water supply. Correct problem, and re-set unit at
HP RESET
14
Summary of Contents for Deluxe OWC2412QC
Page 21: ...PIPING SCHEMATIC 19 ...