SERVICE CORD
All 2OACH-Series units are equipped with a standard 10-foot long service cord
with plug configurations and receptacle requirements as shown in this chart.
2OACH1211, 2OACH1811, 2OACH2412 and 2OACH3612 units come with
LCDI
(Leakage Current Detection & Interruption) devices that serve as a means of
electrical protection.
CAUTION
DO NOT USE THE LCDI AS AN ON/OFF SWITCH FOR THE UNIT
All 3-phase models are equipped with locking plugs for added connection
reliability. Refer to the chart below for plug and receptacle details for all 2OACH
models.
A DAMAGED POWER SUPPLY CORD MUST BE
REPLACED WITH A NEW POWER SUPPLY CORD
AND NOT REPAIRED
UNIT/MODEL
PLUG CONFIGURATION
RECEPTACLE
115 VOLT
2OACH1211
NEMA 5-15R
115 VOLT
2OACH1811
NEMA 5-20R
208-230 VOLT SINGLE PHASE
2OACH2412
NEMA 6-20R
208-230 VOLT SINGLE PHASE
2OACH3612
NEMA 6-30R
208-230 VOLT SINGLE PHASE
2OACH6012
NEMA 6-50R
208-230 VOLT 3-PHASE
2OACH3632
2OACH6032
NEMA L15-30R
460 VOLT 3-PHASE
2OACH3634
2OACH6034
NEMA L16-20R
15A-125 VOLT
NEMA 5-15P
20A-125 VOLT
NEMA 5-20P
20A-250 VOLT
NEMA 6-20P
30A-250 VOLT
NEMA 6-30P
50A-250 VOLT
NEMA 6-50P
30A-250 VOLT
NEMA L15-30P
20A-460 VOLT
NEMA L16-20P
6
ELECTRICAL CONFIGURATION
Summary of Contents for 2OACH Series
Page 26: ...24 PIPING SCHEMATIC...
Page 27: ...25 WIRING SCHEMATIC FOR 2OACH12 18 and 24...
Page 28: ...26 WIRING SCHEMATIC FOR 2OACH3612...
Page 29: ...27 WIRING SCHEMATIC FOR 2OACH6012 DISCHARGE TEMP SENSOR...
Page 30: ...THREE PHASE MONITOR 28...
Page 31: ...29 WIRING SCHEMATIC FOR 2OACH3632...
Page 32: ...30 WIRING SCHEMATIC FOR 2OACH3634...
Page 33: ...31 WIRING SCHEMATIC FOR 2OACH6032...