Océ ProCut Site Prep
Electrical connection – 208 V system with 1-9kW Vacuum Generator
The cutter is connected with one power cord to the power main. The vacuum generator is
connected with one power cord to the power main. The Cutter and Vacuum Generator need
separate circuit breakers. All other devices are connected to the power box of the cutter including
any optional equipment.
•
2 power cords are included in the package content. Customer must supplier connectors to
power supply.
Warning! An electrical hazard exists if an incorrect ground fault interrupter protects the high-
frequency leakage current. See Ground Fault Requirements.
Power
Main supply voltage variance max.
10%
Power consumption - 3 phases
max 12.6kW, typical 5.6kW
Table 6: Power Consumption and Variance
Figure 3: 200V Electrical Connection
“A” Cutter Power box
Value
Unit
Phases 3
Voltage 208
V
Power frequency, pump-depending
50/60
Hz
Power fusing min.
16
A
Wiring
3 phases, L1, L2, L3, N, PE
CEE-Plug
30A, 208V, 5 Poles, Walther Electric Type 230 509
Special-purpose ground fault interrupter required
Fusing current:>30mA per converter
“B” Vacuum Turbine/Generator
Value
Unit
Phases 3
Voltage 208
V
Power frequency, pump-depending
50/60
Hz
Power fusing min.
50
A
Wiring
3 phases, L1, L2, L3, N, PE
CEE-Plug
60A, 208V, 5 Poles, Walther Electric Type 261 509
Special-purpose ground fault interrupter required
Fusing current:>30mA per converter
Table 7: Electrical Connections with 1-9kW Vacuum Turbine/Generator
Océ ProCut Site Preparation Guide - Revision: E
7