AcquiSuite Ally 12 & 48 User Guide (Rev D)
62 |
P a g e
Stop Bit
2, 1
Termination
None provided
Data Formats
Modbus, BACnet MS/TP, Modbus TCP or BACnet IP
Mechanical
Wire Connections
12-22 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated
Mounting
Enclosure or Panel Mount (PS48 only)
High Voltage Cover
IP40
Mounting Plate
Only
Operating Temperature
-20 to + 60
⁰
C (-4 to 140
⁰
F) (the colder the temperature the more voltage needed to
power the board)
Humidity
5% to 95% non-condensing
Enclosure
ABS Plastic, 94-V0 flammability rating, connections sized for 1
–
inch EMT conduit
Dimensions
(L) 33.7cm x (W) 25.2cm x (H) 8.0 cm (13.3” x 10” x 3.1”)
(no enclosure version)
(L) 24.7cm x (W) 25.2cm x (H) 8.0 cm (9.8” x 10” x 3.1”)
(no enclosure version)
PCBA Dimensions
(L) 21.6cm x (W) 21.6.0cm x (H) 6.4 cm (8.5” x 8.5” x 2.5”)
Obvius Ally Configuration Console
™ Minimum System Requirements
Operating System
Windows® 7. Windows® 8, Windows® 10
Communications Port
RS-485 & USB standard. Ethernet available. One USB Port required on PC.
Safety
FCC Compliance
This device has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the user will be
required to correct the interfe
rence at user’s own expense.
Serial/Ethernet Meters
The following are UL Recognized:
AMC12-B-y-z, -P-y-z, AMC48-B-y-z, -P-y-z
The following are UL Listed: AMC12
-C-y-z , AMC48-C-y-z
Conforms to UL Std 61010-1, 3rd Edition, UL 61010-2-30:2010
Certified to CSA Std C22.2 No. 61010-1, 3rd Edition