AcquiSuite Ally 12 & 48 User Guide (Rev D)
50 |
P a g e
C
ONFIGURING
E
LEMENT AND
C
HANNEL
R
EGISTER FOR
S
ERVICE
T
YPES
The Obvius Ally Configuration Console software enforces all element configurations to form a valid
electrical system. Configurations performed by remote systems may produce unexpected results if
configurations are internally inconsistent. The following tables document how to configure element and
channel registers for each service type. Every register should be explicitly written.
Red Text
indicates Required Values,
Purple Text i
ndicates Suggested Defaults if this data is not known.
Modbus Absolute Address/BACnet Object Assignments for Setting up Service Types
REGISTER TEMPLATE
Service Type
2207
V_Input
2217
Description
2617
Channels
Volt Ref
CT Type
Range
Phase Shift CT Multiplier
CT Sign
CH1
2220
2223
2224,2225
2224,2225
2221,2222
2226
CH2
2229
2232
2227,2228
2233,2234
2230,2231
2235
CH3
2238
2241
2236,2237
2242,2243
2239,2240
2244
Configurations
4 Wire 3
ɸ
(Wye)
Service Type
1
V_Input
1
or 2
Description
31 Char
Channels
Volt Ref
CT Type
Range
Phase Shift
CT Multiplier
CT Sign
CH1
L1
–
N
[1]
mV
[1]
or
RōCoil
[2]
Any > 0A
-3.0
˚
to +3.0
˚
Any > 0
[1]
0 or 1
CH2
L2
–
N
[2]
mV
[1]
or
RōCoil
[2]
Any > 0A
-3.0
˚
to +3.0
˚
Any > 0
[1]
0 or 1
CH3
L3
–
N
[3]
mV
[1]
or
RōCoil
[2]
Any > 0A
-3.0
˚
to +3.0
˚
Any > 0
[1]
0 or 1
3 Wire 3
ɸ
(Delta)
Service Type
2
V_Input
1
or 2
Description
31 Char
Channels
Volt Ref
CT Type
Range
Phase Shift
CT Multiplier
CT Sign
CH1
L1
–
N
[1]
mV
[1]
or
RōCoil
[2]
Any > 0A
-3.0
˚
to +3.0
˚
Any > 0
[1]
0 or 1
CH2
L2
–
N
[2]
mV
[1]
or
RōCoil
[2]
Same as 1
Same as 1
Same as 1
0 or 1
CH3
L3
–
N
[3]
mV
[1]
or
RōCoil
[2]
Same as 1
Same as 1
Same as 1
0 or 1
Even though CH2 is calculated internally it is recommended that the CT settings reflect those from CH1 rather than being left at factory default
to facilitate configuration validation from the RTU.