convert the information when generating a report for the user.  

For example, if you wish to draw a graph of KW over Time, prompt the user for a date range, say Jan 1 midnight  to Jan 2 
midnight.  Take the user specified end points and convert these times from Local time to UTC.  Next, create an SQL query 
using the new UTC formatted data as your select statement. ie:

SELECT * from TABLE where time > '2003-01-01 08:00:00' and time < '2003-01-02 08:00:00'

Note the time is 8 hours ahead of local time. This example is for Pacific which is 8 hours off from UTC. This will return a 
list of data points between the two specified time ranges.  Next, plot the data on a graph, using the UTC times for start and 
end points.  Lastly, when drawing the 'time' legend on the graph, convert the values back to Local time before displaying. Ie, 
2003-01-01 00:00:00 to 2003-01-02 00:00:00.  Any division lines on the time axis can be handled the same way.  The 
advantage of using this technique is that it will properly draw a graph across DST change boundaries.  The graph axis is 
based on UTC time with no DST, and will not show a gap or overlap a the time of the change.  The axis labeling will be 
correct as well, matching the UTC times precisely.  

Another way to handle the conversion is to query and convert all the returned timestamps to local time before drawing the 
graph.  This is useful if you do not have detailed control over the graph legend drawing process. This technique will not 
properly graph across DST changes as the graph is based on local time including DST changes.

System logs

The AcquiSuite can keep several log files that report the general operation of the system, not related to the normal data logs. 
These include the following:

Debug Messages:

 The AcquiSuite can run a “syslog” process to record more detailed information about its operations, 

however this log consumes vast quantities of memory quickly, and is disabled by default.  Click the “start log” button to 
enable the feature.  Click the “end log” button to disable.  Note: when the AcquiSuite is rebooted, the debug log will be 
disabled on startup.

Kernel Boot log

:  Startup messages about the Linux operating system startup.  This log shows what hardware items were 

detected and initialized. 

Ftp Connection log: 

This log shows a list of files transferred by FTP on the AcquiSuite.  

Last Data Upload log

: This log file contains a report from the last data upload attempt to remote database/webservers such 

as BMO.  This log will show if any log files are being rejected by the dabase/webserver, or if the network is not allowing a 
connection. 

Last Modem Connection log:

 This log file shows the details of the modem operation including modem connection quality 

parameters.  This is updated ever time the modem makes a dilain or dialout connection.

Time Change Log

:  This log contains a list of time change events. When the AcquiSuite system clock is changed either 

manually or by automated time sync, and the change is more than a few seconds, the event is recorded here.

System boot log: 

This log shows when the AcquiSuite was started, and lists process events such as remote logins, or logger 

process restarts.  This log is most useful for detecting when the AcquiSuite was restarted, and whether there was a proper 
shutdown event prior to rebooting (if not, possibly a power outage).

Start/End logging

: This button allows the user to start detailed logging or disable it if it is running. 

Purge Log Files

:  This button will clear all the system log files listed on this page, but not the meter data log files. (deletes 

kernel, boot, ftp, messages, upload log files)  This does not clear the interval log data from attached meter devices.

Firmware Update

The AcquiSuite can upgrade its own firmware using the firmware update page.   The AcquiSuite must have an Internet 
connection to communicate with the Obvius.com website for firmware updates.  If a LAN connection is present and 
configured, it will be used by default.  

After clicking the “Check for updates” button, the AcquiSuite will contact the obvius.com webserver and attempt to 
download a list of firmware files.  The list is compared to the firmware versions installed, and a listing of the files will be 
displayed.  If any firmware updates are available, a button to the right will be shown labled “Upgrade”.  The firmware files 
are as follows:

asarm.cramfs The main AcquiSuite firmware file including the modbus and data logging software 
usrarm.cramfs High level system support files such as FTP, and timezone information
ramdisk.gz

Low level system files and system libraries

Page 21

A8810 AcquiSuite – Data Acquisition Server

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for AcquiSuite A8810

Page 1: ...quisition Server Obvius LLC Installation and Operation Manual Model A8810 Date Jan 15 2013 Page 1 A8810 AcquiSuite Data Acquisition Server www GlobalTestSupply com Find Quality Products Online at sale...

Page 2: ...repaired altered or modified outside of Obvius s authorized facilities 4 has not been sold subject to other warranty terms specified at the time of sale and 5 is still owned by the original purchaser...

Page 3: ...Troubleshooting Ethernet Problems 19 System Options 20 Status 20 Processes 20 Date and Time 20 Universal Time Is Your Friend 20 System logs 21 Firmware Update 21 Diagnostics 22 Host Lookup 22 Connecti...

Page 4: ...long RS485 runs over 200ft LAN information Ethernet 10 100Mbit connection point hub or switch IP address and Netmask check with system administrator Gateway address check with system administrator DN...

Page 5: ...The RJ45 Ethernet is isolated to 1500VDC from the main board RS485 port is isolated to 1500VDC from the main board Power input and USB port and are non isolated Environmental Pollution Degree 2 Altit...

Page 6: ...e a minimum insulation rating that exceeds the voltage inside the panel In addition other regulations may apply consult the building codes in your area prior to installation The RS485 port on the A881...

Page 7: ...f when not connected Blinks when Lan traffic is being sent or received RS485 RX TX The 485TX led should blink slowly once per second during normal operation The RX led will blink when external Modbus...

Page 8: ...computer such as a laptop primary connection will be dialin or dialout by modem You will need the following information from your network administrator The addresses will be in the form of where refer...

Page 9: ...t to allow the AcquiSuite to reboot Once the AcquiSuite has rebooted the new IP address will be displayed on the console If DHCP addressing was specified the server assigned address will be displayed...

Page 10: ...tton B In the network setup dialog there should be a list of items including adapters clients and protocols Locate the item labeled Internet Protocol TCP IP Note If you have multiple ethernet cards yo...

Page 11: ...These include the 4 20mA device scale multipliers and engineering units Each 4 20mA or 0 10Vsensor should be supplied with technical information including the low and high range values that can be use...

Page 12: ...number and firmware version when available for all devices in the Modbus device list Show stats show packet counters for all devices in the device list These include Sent Total number of packets sent...

Page 13: ...Alarm Specify a threshold for the alarm If the data point is recorded below the Low Alarm or above the High Alarm levels at the time a log entry is taken the point will be considered in an alarm stat...

Page 14: ...he log period is not calculated based on 15 minutes after the last reading When the AcquiSuite is first started it will take an initial reading of all the Modbus devices immediately Following that the...

Page 15: ...for Modbus RS485 Devices This option allows the AcquiSuite to search for Modbus devices attached on the RS 485 port This feature may be disabled to reduce queries on the RS 485 port Default is enabled...

Page 16: ...sensor s serial number Each sensor may be given a name and some have additional options to configure such as input value scaling ModHopper Map The AcquiSuite has additional diagnostic features that a...

Page 17: ...server provided by your dialup isp If you only use the AcquiSuite on a crossover cable and or dialin mode you should leave these blank DHCP enable disable If you LAN has a DHCP server you may enable...

Page 18: ...synchronization will align the clock to within 1 second of the internet time source or atomic clock You may need to verify if your firewall will allow NTP or Rdate packets to pass through Generally i...

Page 19: ...ion log This log shows a list of files transferred by FTP on the AcquiSuite Last Data Upload log This log file contains a report from the last data upload attempt to remote database webservers such as...

Page 20: ...s will be printed in Green failure messages will be printed in Red A sample upload test follows Ping localhost 127 0 0 1 Success Ethernet IP address 192 168 10 50 mask 255 255 255 0 Local subnet 192 1...

Page 21: ...e cursor to the right one space If you press the select button multiple times the cursor will move right a similar number of spaces allowing you to skip over characters that may be correct based on th...

Page 22: ...rds that have been configured and will return the AcquiSuite to the factory default settings This is mainly useful when reconfiguring an AcquiSuite that has been used previously on a different job or...

Page 23: ...he log file but may be several seconds after the initial log cycle The log date time is in Universal time UTC This means that the data is logged with no shift for daylight savings time and must be con...

Page 24: ...lid data point Log Storage Capacity The AcquiSuite uses approximately 8 Mbytes of flash disk for log file storage As data from the modbus meters is collected it is appended to log files on this flash...

Page 25: ...on as needed Note if configuration changes are made to the AcquiSuite those changes will be uploaded to the BMO site If configuration changes are made at both the AcquiSuite and the BMO website the mo...

Page 26: ...on your computer as well as provide configuration information about the AcquiSuite Enertrax DL can also be configured to make LAN or Dilaup calls to one or more AcquiSuite or AcquiLite data acquisiti...

Page 27: ...ify a command prompt prior to using mdel that will prevent the FTP client software from asking if you are sure you wish to delete each file Linking to AcquiSuite Device Status Pages It may be helpful...

Page 28: ...y 4 x 4 25 x 2 deep The AcquiSuite has 4 mounting holes for use with a 6 screw The drawing above shows the relative position of the mounting holes Page 30 A8810 AcquiSuite Data Acquisition Server www...

Reviews: