Troubleshooting Modbus Devices

If the device you have attached does not appear in the Modbus device list, check the following:

Verify the + (red), - (black), and Shield connections are correct on all connections.  Look for any connection in the 
middle of the loop that may have the wires reversed, or shorted together.   Check the Modbus faq on the obvius.com 
website for further details on wiring a Modbus serial connection. 

Verify the address settings of every Modbus device. No two devices may have the same address.  

If only one device is not working, try disconnecting all the other devices on the Modbus loop to isolate the problem.  If 
possible, bring the failed device adjacent to the AcquiSuite and attach it with a short stub of wire to eliminate possible 
wiring problems.   If the AcquiSuite can find a device on the short stub, the problem is probably a wiring related issue on 
the RS485 loop.

Check to verify the Modbus device is supported by the AcquiSuite. Usually, the AcquiSuite will locate the device and 
print “Unknown” in the device status column if the device is not recognized by the AcquiSuite firmware drivers.  In the 
lower right corner of this screen, there is a link that will show a list of supported devices.  Use this to verify the Modbus 
device in question is supported by the AcquiSuite firmware version.  If not, check for firmware upgrades online with the 
Firmware Update configuration page. 

Remember, the AcquiSuite may take between 2 and 5 minutes to detect a new device that has been attached to the 
Modbus rs485 loop.  Rebooting the AcquiSuite, refreshing the device list page, or using the console  'Modbus status' 
menu will not speed up the recognition process. 

Click the “Troubleshooting” link at the bottom of the Modbus device list page for further diagnostics.

Modbus Setup

The Modbus setup page provides several options related to the Modbus RS485 serial port.

AcquiSuite Name: 

This is the name of the AcquiSuite.  This name will be present on all log file descriptors when uploaded 

to a central database website such as BMO.  It is helpful to name the AcquiSuite based on the physical location of the 
system, or building.  Note: this feature was labeled “Loop Name” in older firmware versions.

Data logging period:

 This option sets the log interval for the AcquiSuite.  Options range from once per minute to once per 

hour. All  of the selections are even divisions of one hour.  The AcquiSuite calculates the next log time by finding the next 
multiple of the log period past the start of the hour.  For example, if the log period is 15 minutes,  log readings will be taken 
at 0, 15, 30 and 45 minutes past the hour.  The  log period is not calculated based on “15 minutes after the last reading”

When the AcquiSuite is first started, it will take an initial reading of all the Modbus devices immediately. Following that, the 
next log reading will be calculated as a multiple of the log period after the hour.  The initial reading is taken to allow the 
AcquiSuite to gather information for meters that require demand calculations, as well as provide accurate information 
starting when the AcquiSuite is booted. 

Modbus/TCP access:

 The AcquiSuite has a Modbus TCP gateway feature that allows other systems to send queries to all 

attached Modbus RS485 devices.  This feature allows control of what systems have access to the Modbus TCP gateway 
feature.  The settings include “no access”, “local subnet only” and “allow any”.   This basic security feature only allows 
control based on the IP address of the system making the request.  The Modbus TCP protocol does not have provisions for 
any authentication password or other methods of security.  By default, the gateway feature is disabled, and set to “No 
Access.”

The Modbus TCP gateway is a feature that allows the AcquiSuite to share the attached Modbus RS485 devices with other 
systems such as PCs with software and building control systems. The gateway receives incoming TCP requests, verifies the 
length of the packet does not exceed 255 bytes, and forwards the packet to the Modbus RS485 loop.  The gateway does not 
verify the contents of the packet, nor the target address specified in the request.   If the Modbus RS485 device sends a valid 
response back, the gateway will return this information to the the system requesting it via TCP.  If no response is received, a 
timeout failure will be sent to the requester.  Because the gateway does not process the contents of the request or reply, it is 
possible to query devices on the Modbus RS485 loop that are not specifically supported by the AcquiSuite.   A Modbus/TCP 
technical guide may be available soon at 

Modbus RS/485 baud rate

: This feature allows the configuration of the RS485 serial port speed which the AcquiSuite uses 

to communicate with Modbus devices.  Options include 

9600

19200

38400, 57600, 

and

 115200

.  The default is 9600, most 

Modbus devices communicate at this speed as well.   Multiple baud rates may be selected in this menu. If multiple rates are 
selected, the AcquiSuite will automatically detect the baud rate of each Modbus device from the chosen options.  Once the 
baud rate has been detected for a specific Modbus device address, and  will continue to communicate with that specific 
device address at the detected speed.  This feature will allow you to mix multiple devices on the same RS485 loop with 

Page 16

A8810 AcquiSuite – Data Acquisition Server

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for AcquiSuite A8810

Page 1: ...quisition Server Obvius LLC Installation and Operation Manual Model A8810 Date Jan 15 2013 Page 1 A8810 AcquiSuite Data Acquisition Server www GlobalTestSupply com Find Quality Products Online at sale...

Page 2: ...repaired altered or modified outside of Obvius s authorized facilities 4 has not been sold subject to other warranty terms specified at the time of sale and 5 is still owned by the original purchaser...

Page 3: ...Troubleshooting Ethernet Problems 19 System Options 20 Status 20 Processes 20 Date and Time 20 Universal Time Is Your Friend 20 System logs 21 Firmware Update 21 Diagnostics 22 Host Lookup 22 Connecti...

Page 4: ...long RS485 runs over 200ft LAN information Ethernet 10 100Mbit connection point hub or switch IP address and Netmask check with system administrator Gateway address check with system administrator DN...

Page 5: ...The RJ45 Ethernet is isolated to 1500VDC from the main board RS485 port is isolated to 1500VDC from the main board Power input and USB port and are non isolated Environmental Pollution Degree 2 Altit...

Page 6: ...e a minimum insulation rating that exceeds the voltage inside the panel In addition other regulations may apply consult the building codes in your area prior to installation The RS485 port on the A881...

Page 7: ...f when not connected Blinks when Lan traffic is being sent or received RS485 RX TX The 485TX led should blink slowly once per second during normal operation The RX led will blink when external Modbus...

Page 8: ...computer such as a laptop primary connection will be dialin or dialout by modem You will need the following information from your network administrator The addresses will be in the form of where refer...

Page 9: ...t to allow the AcquiSuite to reboot Once the AcquiSuite has rebooted the new IP address will be displayed on the console If DHCP addressing was specified the server assigned address will be displayed...

Page 10: ...tton B In the network setup dialog there should be a list of items including adapters clients and protocols Locate the item labeled Internet Protocol TCP IP Note If you have multiple ethernet cards yo...

Page 11: ...These include the 4 20mA device scale multipliers and engineering units Each 4 20mA or 0 10Vsensor should be supplied with technical information including the low and high range values that can be use...

Page 12: ...number and firmware version when available for all devices in the Modbus device list Show stats show packet counters for all devices in the device list These include Sent Total number of packets sent...

Page 13: ...Alarm Specify a threshold for the alarm If the data point is recorded below the Low Alarm or above the High Alarm levels at the time a log entry is taken the point will be considered in an alarm stat...

Page 14: ...he log period is not calculated based on 15 minutes after the last reading When the AcquiSuite is first started it will take an initial reading of all the Modbus devices immediately Following that the...

Page 15: ...for Modbus RS485 Devices This option allows the AcquiSuite to search for Modbus devices attached on the RS 485 port This feature may be disabled to reduce queries on the RS 485 port Default is enabled...

Page 16: ...sensor s serial number Each sensor may be given a name and some have additional options to configure such as input value scaling ModHopper Map The AcquiSuite has additional diagnostic features that a...

Page 17: ...server provided by your dialup isp If you only use the AcquiSuite on a crossover cable and or dialin mode you should leave these blank DHCP enable disable If you LAN has a DHCP server you may enable...

Page 18: ...synchronization will align the clock to within 1 second of the internet time source or atomic clock You may need to verify if your firewall will allow NTP or Rdate packets to pass through Generally i...

Page 19: ...ion log This log shows a list of files transferred by FTP on the AcquiSuite Last Data Upload log This log file contains a report from the last data upload attempt to remote database webservers such as...

Page 20: ...s will be printed in Green failure messages will be printed in Red A sample upload test follows Ping localhost 127 0 0 1 Success Ethernet IP address 192 168 10 50 mask 255 255 255 0 Local subnet 192 1...

Page 21: ...e cursor to the right one space If you press the select button multiple times the cursor will move right a similar number of spaces allowing you to skip over characters that may be correct based on th...

Page 22: ...rds that have been configured and will return the AcquiSuite to the factory default settings This is mainly useful when reconfiguring an AcquiSuite that has been used previously on a different job or...

Page 23: ...he log file but may be several seconds after the initial log cycle The log date time is in Universal time UTC This means that the data is logged with no shift for daylight savings time and must be con...

Page 24: ...lid data point Log Storage Capacity The AcquiSuite uses approximately 8 Mbytes of flash disk for log file storage As data from the modbus meters is collected it is appended to log files on this flash...

Page 25: ...on as needed Note if configuration changes are made to the AcquiSuite those changes will be uploaded to the BMO site If configuration changes are made at both the AcquiSuite and the BMO website the mo...

Page 26: ...on your computer as well as provide configuration information about the AcquiSuite Enertrax DL can also be configured to make LAN or Dilaup calls to one or more AcquiSuite or AcquiLite data acquisiti...

Page 27: ...ify a command prompt prior to using mdel that will prevent the FTP client software from asking if you are sure you wish to delete each file Linking to AcquiSuite Device Status Pages It may be helpful...

Page 28: ...y 4 x 4 25 x 2 deep The AcquiSuite has 4 mounting holes for use with a 6 screw The drawing above shows the relative position of the mounting holes Page 30 A8810 AcquiSuite Data Acquisition Server www...

Reviews: