Value 0=No
Value 1=Yes
40050 M_CONTACT
W/R
R
2
0
1
0
Level START contact
Value 0=NO
Value 1=NC
40051 M_CONTACT
W/R
R
2
0
1
0
Level STOP contact
Value 0=NO
Value 1=NC
40052 M_YES_NO
W/R
R
2
0
1
1
Menù light
Value 0=No
Value 1=Si
40053 M_BAUD
R
R
2
0
6
0
Baudrate MODBUS
Value 0=2400
Value 1=4800
Value 2=Verde
Value 3=Rosa
Value 4=Azzurro
Value 5=Blu
40054 M_TIME_S
W/R
R
2
1
120
120
s
Pulses time out in pulse mode,
PPM mode, concentration mode e
MLQ mode
40055 M_AMPERE
W/R
R
2
10
35
20
Motor current calibration window
40056 M_50_60Hz
W/R
R
2
0
1
0
50/60 Hz
40057 M_LP_PL
W/R
R
2
0
1
0
L/pulse pulse/L in PPM, MLQ e
percentage modes
40058 M_U8
R
R
2
1
247
1
MODBUS ID
41001 OPERATING
MODE
W/R
W/R
2
1
10
1
uint16
Operating modes
Value 1=Constant
Value 2=Batch
Value 3=Pause-work
Value 4=Weekly
Value 5=Analog mA
Value 6=Analog V
Value 7=PPM
Value 8=Percentage
Value 9=MLQ
Value 10=Pulse
41002 START-STOP
W/R
W/R
2
0
2
0
uint16
Starting motor
Value 0=Stop
Value 1=Start
Value 2=Standby
41003 ALARMS
W/R
W/R
4
This value can be
written only to 0
uint3
These registers inform the user
about alarms according to the
position of the bit
41004
BIT 0
"UVG17",//UNDER BUS
GO
BIT 1
"UVB18",//UNDER BUS
GO
BIT 2
"TOU01",//TIME OUT