OBID
i-
scan
®
HF
Installation
ID ISC.ANT1800/700-A/-B
FEIG ELECTRONIC GmbH
Seite 52 von 71
M00910-8e-ID-B.doc
Configuration and Test in ISO-Host or Buffered Read
Step
Action
Note
1
Select „Configuration“
2
Host Interface
Set RS485 to “False”
„Enable Termination
Resistors
“
The RS232/485 Settings
should be set to:
Busaddress=0,
Baudrate=38400 baud,
Parity = even ,
Number of Databits = 8,
Number of Stopbits = 1
3
Confirm with „Apply“
4
Peripheral Devices
Set People Counter
to„True“ and
Detection Mode for Ext.
I/O-
Boards to “Search up to
Busaddress 1”
5
Confirm with „Apply“
6
Peripheral Device
Digital IO:
Setting Time:
„Setting Time“ set the dura-
tion time for the alarm.
(10 means 1 second)
(e.g. 10 x 100ms)
Assign
Output 1 to antenna 1.
Output 2 to antenna 2.
Output 3 to antenna 3.
„True“ means: Output 1,2
or 3 will be active if the
reader read a valid trans-
ponder on the correspond-
ing antenna