This product must also be connected to a Ground Fault protected outlet with the detector in the main circuit breaker box
(not on the circuit). (NOTE: GFCI ON THE TABLE ALONE IS NOT SUFFICIENT FOR YOUR SAFETY.) If it should mal-
function or break down, grounding provides a path of least resistance for electrical current to reduce the risk of electric
shock. This product is equipped with a cord having an equipment-grounding conductor and a grounding pin. The pin must
be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordi-
nances. See U.S. sample below.
Risk of Electric Shock - Connect this furnishing to a Ground Fault Protected Outlet only.
DANGER
GROUNDING
The integral GFCI should be tested on a routine basis. To test the GFCI, push the test button. The GFCI should interrupt
power. Push the reset button. Power should be restored. If the GFCI fails to operate in this manner,DO NOT USE THE
UNIT Disconnect the unit and have the problem corrected by a qualified service representative or an electrician before
using.
Improper connection of the equipment-grounding conductor can result in a risk of electric shock. Check with a qualified elec-
trician or service person if you are in doubt as to whether the product is properly grounded. Do not modify the plug provided
with the product - if it will not fit the outlet; have a proper outlet installed by a qualified electrician.
Correct Implementation
Incorrect Implementation
Grounding Methods
6
INSTALLATION
FACILITY ELECTRICAL INSTRUCTIONS
CAUTION
When installed in the United States, the electrical wiring of this table must meet the requirements of the
National Electric Code (NEC) and any applicable state or local codes. The electrical circuit providing
115V/15A power (230V overseas) to this table must be protected by a GFCI (ground fault interrupter
circuit) installed by a qualified electrician. Installation should be approved by a local building/electrical/
plumbing inspector.
FACILITY CONNECTION REQUIREMENTS:
1. An electrical circuit protected by a GFCI circuit breaker as required by state or local codes.
PROCEDURE:
a. The table is equipped with a 3ft power cord which may be plugged into either a wall outlet or floor GFCI. If located
on the floor, the following location is recommended.
Recommended
area for floor
installed GFCI pro-
tected outlet
24”
6”
6”
19”