background image

 

 

Contact Information 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OLE (UK) Ltd,

 

 

 

Barns A & B, 

Bowely Farm, 

Bowely Lane, 

South Mundham, 

Chichester, 

West Sussex, 

United Kingdom 

PO20 1NB 

 

  

+44 (0)1243 267930 

 

 

[email protected]

 

 

Summary of Contents for T4000

Page 1: ...O L E UK Ltd T4000 INSTRUCTION INSTALLATION MANUAL Revision 02 Date 01 10 2019 ...

Page 2: ...e 5 Medium Controller can be used in 5 Technical Features 5 T4000 240PR 240AL 5 T4000 24PR 24AL 5 T4000 12ALSP 5 Description of Operation 6 Connection Settings 6 Inputs Each of the 4 inputs can be set to 6 Siren and BMS Outputs 7 Alarm Mute 7 Test Mode 7 Pump Control Mode 8 T4000 T5020 Pump controller 10 T4000 Wiring Diagram Setting for Day Tank Control 11 T4000 Wiring Diagram Setting for WASTE Ta...

Page 3: ...Contact Information OLE UK Ltd Barns A B Bowely Farm Bowely Lane South Mundham Chichester West Sussex United Kingdom PO20 1NB 44 0 1243 267930 sales oleuk com ...

Page 4: ...liance of 240vac and 24vdc This appliance must be installed and serviced by a competent electrical technician to the current requirements of BS761 and IEEE recommendations Before servicing this appliance normal safe isolation procedures should be implemented It is recommended that suitable circuit protection is installed and should include as a minimum a suitable earth overcurrent protection and a...

Page 5: ...e 1 the distance between mounting holes is 110mm wide X 160mm high PSU Wiring The T4000 has the option of coming with a 240vac to 24vdc PSU as shown below in Figure 1 if a PSU is supplied then 240vac should be wired into the LNE terminals the output of the PSU is 24vdc and the terminals should be wired to the terminals of the T4000 as shown in Figure 2 Figure 1 ...

Page 6: ...and Size 2 x m16 1 x m20 Operating Temperature 0 60 C I P protection degree IP 65 Nominal Voltage 240Vac Frequency 50 60Hz Relay Max Contact Voltage AC 240vac Relay Max Contact Voltage DC 24vdc Relay Max Current 10Amps Nett Weight 0 6kg T4000 24PR 24AL Enclosure Size 125 x 175 x 75 Cable Gland Size 2 x m16 1 x m20 Operating Temperature 0 60 C I P protection degree IP 65 Nominal Voltage 24vdc Relay...

Page 7: ...00 can be used as a Pump controller or as an Alarm When in Pump control mode the Relay outputs 2 and 3 are not operational When input 4 is in Pump control this also shuts down the Pump Circuit Fail Safe Connection Settings Float switches provided by OLE are Normally Closed NC When in the Down position The T4000 inputs can be switched from NC to NO as required using the 2 jumpers on each circuit Se...

Page 8: ...e when the LED s are Green and in the safe operation mode This ensures BMS systems and similar control monitors can see when they are made safe and not simply acknowledged locally Alarm Mute The T4000 has the capability of muting the audible alarm without deactivating The remote output by simply pushing the ALARM MUTE button the sounder will be Muted until the button is depressed Test Mode The T40...

Page 9: ...g the position of the jumpers as shown in Figure 2 When control input 2 is triggered this latches the pump control relay on When control input 3 is triggered this unlatches the pump control relay As a failsafe if input 4 is triggered the audible alarm will sound and the pump control relay will open circuit ...

Page 10: ...Page 9 of 14 Figure 2 ...

Page 11: ...p controller You can configure a T5020 with a R5 relay board in conjunction with a T4000 as shown in Figure 3 to provide a visual indication of the tank level in Litres when used in this mode no float switches are required Figure 3 ...

Page 12: ...mp controller or as an Alarm 5 H H is for an Audible Alarm that will activate when Flashing RED condition is present This is the supply voltage so 24vdc Operation 1 When lights are GREEN No Alarm 2 When Lights Flash RED Alarm problem ORANGE PUMP ON 3 When the Acko button is pressed the Lights changed to fixed RED This Auto resets when Alarm condition is removed 4 The BMS output MC changes conditio...

Page 13: ...r as an Alarm 5 H H is for an Audible Alarm that will activate when Flashing RED condition is present This is the supply voltage so 24vdc Operation 1 When lights are GREEN No Alarm 2 When Lights Flash RED Alarm problem ORANGE PUMP ON 3 When the Acko button is pressed the Lights changed to fixed RED This Auto resets when Alarm condition is removed 4 The BMS output MC changes condition Volt Free whe...

Page 14: ...ch is a 12vdc lead acid battery unit which is continuously being charged by a solar panel power to the T4000 is initiated when the button on the front of the unit is pressed which then keeps the power to the T4000 for a predetermined programmed time Please see the TXX 12VPS T manual for full operational details T4000 12ALSP unit wired to a T4000 ...

Page 15: ...s Q Can any type of level switch be used on the T4000 A Yes If the switches are simple apparatus meaning reed switch or similar Not capacitive or resistance type Q Can the T4000 Pump directly A The T4000 can switch up to 10Amps at 250V nothing with a greater current draw and working voltage above these values should be switched if the circuit load is more than the allowed a separate contactor shou...

Reviews: