6
•
All Power conditioners enclosure are IP40 rated.
4.0 POWER CONDITIONER RATING CHART
Model Number
Input voltage 1-
phase
Output
Voltage
Max
output
current
Circuit
Breaker
rating
Minimum
Conductor Size Frequency
NPT2000-H-NS
208 or 240 VAC
208,
240/120
VAC
9.6 A
15 A
14 AWG
60 Hz
NPT2300-H-NS
208 or 240 VAC
240/120
VAC
9.6 A
15 A
14 AWG
60 Hz
NPT2500-H-NS
208 or 240 VAC
208,
240/120
VAC
12.0 A
15 A
14 AWG
60 Hz
NPT2800-H-NS
208 or 240 VAC
240/120
VAC
12.0 A
15 A
14 AWG
60 Hz
NPT3000-H-NS
208 or 240 VAC
208,
240/120
VAC
14.4 A
20 A
12 AWG
60 Hz
NPT3300-H-NS
208 or 240 VAC
208,
240/120
VAC
16.0 A
20 A
12 AWG
60 Hz
NPT3500-H-NS
208 or 240 VAC
240/120
VAC
14.4 A
20 A
12 AWG
60 Hz
NPT3800-H-NS
208 or 240 VAC
240/120
VAC
16.0 A
20 A
12 AWG
60 Hz
NPT5000-H-NS
208 or 240 VAC
208,
240/120
VAC
24.0 A
30 A
10 AWG
60 Hz
NPT5800-H-NS
208 or 240 VAC
240/120
VAC
24.0 A
30 A
10 AWG
60 Hz
NPT6000-H-NS
208 or 240 VAC
208,
240/120
VAC
29.0 A
40 A
8 AWG
60 Hz
NPT7000-H-NS
240 VAC
240/120
VAC
29.0 A
40 A
8 AWG
60 Hz
H (Indicates Hard-Wired input output model)