![nvent SCHROFF 11990-19 Series User Manual Download Page 66](http://html1.mh-extra.com/html/nvent/schroff-11990-19-series/schroff-11990-19-series_user-manual_1720736066.webp)
11990-190/192
Technical Data
62
R1.0, October 2018
10 Technical Data
Table 17: Technical Data
Physical Dimensions
See drawing
Weight
Shelf weight completely assembled
approx. 35 kg
Power
Input voltage
-40 VDC …. -72 VDC
Input Power
210 A per power feed (Each power feed
is divided internally at the PEM in 6 out-
put branches with 35 A each)
Overcurrent Protection
50 A fuses on PEM
Environmental
Ambient temperature (long term)
+5°C…+40°C (41°F to 104°F)
Ambient temperature (short term)
-5°C…+55°C (23°F to 131°F)
Humidity
+5%...+85%, no condensation
EMI
Conducted Emissions
EN 55022 Class A
Radiated Emissions
EN 55022 Class A
Safety
Protected Earth Test
EN50514, test current 25 A,
resistance <100 mOhm
Hipot Test
EN60950-1, 1000 VDC