nvent ERICO 5RF363N Installation And Operating Instructions Manual Download Page 15

nVent.com/ERICO 

|

 15

6.7 SRFS ON SUB-CIRCUITS

Where SRFs are installed to protect equipment on a particular 
sub-circuit, it is strongly recommended that additional 
protection be installed at the power point of entry. Primary shunt 
protection at the point of entry should be used to divert the peak 
surge currents away from the sub-circuit. This will reduce the 
risk of cross-coupling of transients onto adjacent circuits and 
will reduce the risk of flashover between the locally grounded 
chassis and the earth circuit.

Figure 13 details the role of point of entry protection in these 
instances. The cables supplying the input to the SRF and the 
connection to the earthing system will carry a proportion of the 
surge energy which has been let through the primary  
point-of-entry protector.
Care should be taken therefore, in the routing of these cables to 
ensure that this energy will not couple onto adjacent circuits.

In some instances it will be necessary to provide a separate 
earth electrode for the SRF (subject to compliance with 
relevant wiring regulations), particularly where the filter is to be 
installed on a sub-circuit some distance from the existing earth 
electrode. In this instance, the new electrode should be located 
as near as possible to the SRF. This secondary electrode must 
be electrically bonded to the existing earthing system via the 
most direct route possible, using flat copper tape, and should  
be buried to an appropriate depth.

This earthing arrangement is depicted in Figure 13. If a 
secondary earth cannot be installed, or the earth impedance 

through the sub-circuit to the earth is significantly above 10Ω 

special care must be taken. The risk of flashover between the 
locally grounded chassis and the earth circuit may exist. 
Careful attention must be paid to equipotential bonding of  
the protected equipment.

Figure14. Earthing of an SRF remote from MEN point. Subject to compliance with relevant national stan-

dards). Care is needed ro avoid earth loops within protected environment.

Figure13. Operation of primary shunt protection and SRFs on sub-circuit

Installation and Operating Instructions

Summary of Contents for ERICO 5RF363N

Page 1: ...nVent com ERICO 1 SRF N Series Surge Reduction Filters Installation and Operating Instructions...

Page 2: ...RODUCTION 3 2 WARNING 3 3 INSTALLATION CAUTIONS 4 4 IDENTIFY THE DISTRIBUTION SYSTEM 5 5 MOUNTING THE SRF 8 6 OPTIMISING PERFORMANCE 9 7 SERVICING AND TROUBLESHOOTING 16 8 BACKPLANE MODELS 18 9 SCHEMA...

Page 3: ...US VOLTAGES EXIST WITHIN THE SRF ENCLOSURE THIS UNIT SHOULD BE INSTALLED SERVICED ONLY BY QUALIFIED PERSONNEL AND IN ACCORDANCE WITH RELEVANT NATIONAL ELECTRICAL SAFETY CODES ALL INSTRUCTIONS MUST BE...

Page 4: ...oltages causing problems such as excessive heat build up Because the harmonic waveforms contain higher order frequencies capacitive leakage currents may increase to above prescribed limits and shorten...

Page 5: ...from the load equipment or sub distribution point back to the point of entry and perhaps to the supply transformer the type of distribution system should be identifiable with the aid of the following...

Page 6: ...o this PE conductor Figure 4 TN C S system In this system a separate neutral and protective earth functions combine in a single PEN conductor This system is also known as a Multiple Earthed MEN system...

Page 7: ...om country to country it is important to ensure that the installation complies with all regulations applicable to the location Please seek further assistance if uncertain Regulations differ between co...

Page 8: ...abling and upstream over current protection requirements and all instructions provided in this manual should be taken into consideration before mounting the SRF To preserve the IP rating SRF units fro...

Page 9: ...on the external side surface of the enclosure The cabling and earth wires connected to the filter input should always be run separately with a minimum clearance of 300mm between them and all other cab...

Page 10: ...lock 25 to 120 mm2 19 N m Backplane Stud 1 x M8 8 5 N m 500A Stud Terminal Block 1 x M10 30 N m Backplane Stud 1 x M10 17 N m 800A Stud Terminal Block 2 x M10 30 N m Backplane Stud 1 x M10 17 N m SING...

Page 11: ...nVent com ERICO 11 SRF163N SRF3500N 2X CABLE TIE HOLES ON BACK PLANE TO FASTEN EARTH CABLE IN POSITION OUTPUT INPUT 6 2 CABLING Figure 9 Typical earth cabling Installation and Operating Instructions...

Page 12: ...one A similar scenario exists where the output of the SRF is fed to an electrically noisy load Any transients developed by this load may also be fed to other equipment connected to the same supply Ele...

Page 13: ...by the earthing system to which it is connected A low impedance route to the earth is required less than 10 This can be achieved by ensuring that the earth electrode system at the site presents a low...

Page 14: ...away from the input circuit and any other current carrying conductors Alarm contact ratings 5A 250VAC 54 30 VDC 4kV Isolation See section 7 Servicing and Trouble Shooting for further information Unde...

Page 15: ...provide a separate earth electrode for the SRF subject to compliance with relevant wiring regulations particularly where the filter is to be installed on a sub circuit some distance from the existing...

Page 16: ...fuse should be obtained from nVent as soon as possible Note that the N E Spark Gap does not have an LED SECONDARY UNITS The Secondary Units are blue in colour and contain the secondary shunt diverter...

Page 17: ...UNIT PHASE 1 SRFSUAC UNIT SRF3500N SECONDARY UNIT FUSES N E SPARK GAP PHASE 1 SPARK GAP SECONDARY UNIT FUSE SRF163N GREEN STATUS INDICATING LED DIVERTER MODULE STATUS INDICATING FLAG ALARM CONTACTS O...

Page 18: ...model number These units are supplied without the proprietary enclosure and are intended to be mounted in a customer s provided switchboard SINGLE PHASE SRF MODELS FUSE SECONDARY UNIT SG PRIMARY DIVE...

Page 19: ...the top surface and the outputs on the bottom surface See Section 6 2 Cabling SRF Model Enclosure Size mm Mounting mm W H D X1 X2 Y1 Y2 Fastener Diameter Weight Kg SRF163N 400 300 200 360 470 260 370...

Page 20: ...ctive Lightning Protection System nVent ERICO SYSTEM 2000 Conventional Lightning Protection System 6 Protect Low Voltage Data Telecommunications Circuits 1 4 2 5 3 6 Capture the Lightning Strike Prote...

Reviews: