nvent ERICO 5RF363N Installation And Operating Instructions Manual Download Page 14

14 

|

  nVent.com/ERICO

6.5 CONNECTION OF ALARM CIRCUITS

6.6 INSTALLATION ARRANGEMENT FOR AUSTRALIAN MEN SYSTEMS

The SRF secondary surge diverters are continuously monitored 
and their internal protection status is identified by the green LED 
on each phase blue secondary Unit (SRFSUAC for phase 1, and 
SRFSU on phases 2 and 3 if present).
Reduction in surge handling capacity activates a set of voltage 
free alarm contacts which can be used to shut down the load or 
to activate an external warning.
When mains voltage is applied to the SRF and the surge 
diverters are fully functional, the alarm contacts will be in the 
energized or normal state. The NC contact will be in short circuit 
with the COM contact. Should the surge handling capacity 
fall to below the alarm threshold, these contacts will be in the 
de-energised or alarm state and the NO contact will be in short 
circuit with the COM contact.

The contacts are  "Fail-Safe ' in that, if power to the unit fails, the 
contacts will revert to the de-energised or alarm state.
The alarm contacts should only be connected by an 
appropriately qualified person owing to the possibility of mains 
voltage being present in the SRF cabinet. Care should be taken 
to route the alarm wiring away from the input circuit and any 
other current-carrying conductors.
Alarm contact ratings: 
•  5A 

@

 250VAC

•  54 @ 30 VDC
•  4kV Isolation
See section 7  "Servicing and Trouble Shooting " for further 
information.

Under Australian Standards classification, SRFs are considered 
a piece of equipment to be connected to the mains supply. They 
are not intended for use as switchboards, distribution boards or 
other equipment. As these devices are classified as  "electrical 
equipment AS 3000 Wiring Regulations apply to the installation 
and operation of the units.
AS 3000 specifies minimum requirements for electrical 
equipment that is connected to switch boards or distribution 
boards. For a point of entry application in the multiple earth 

neutral (MEN) distribution system, the SRF equipment should 
be installed as close as possible after the MEN point and after 
both the main disconnect switch/over-current protector and any 
metering equipment. The SRF therefore, may not be installed at 
the physical  "point of entry " of the mains power to the building. 
It must be earthed and installed in accordance with all other 
applicable electrical and safety standards. As the protection 
equipment is hardwired, the installation must be inspected by  
an appropriately authorized electrical authority official prior  
to commissioning.

Figure 12. Typical connection detail for SRF point of entry installation in MEN system.

Installation and Operating Instructions

Summary of Contents for ERICO 5RF363N

Page 1: ...nVent com ERICO 1 SRF N Series Surge Reduction Filters Installation and Operating Instructions...

Page 2: ...RODUCTION 3 2 WARNING 3 3 INSTALLATION CAUTIONS 4 4 IDENTIFY THE DISTRIBUTION SYSTEM 5 5 MOUNTING THE SRF 8 6 OPTIMISING PERFORMANCE 9 7 SERVICING AND TROUBLESHOOTING 16 8 BACKPLANE MODELS 18 9 SCHEMA...

Page 3: ...US VOLTAGES EXIST WITHIN THE SRF ENCLOSURE THIS UNIT SHOULD BE INSTALLED SERVICED ONLY BY QUALIFIED PERSONNEL AND IN ACCORDANCE WITH RELEVANT NATIONAL ELECTRICAL SAFETY CODES ALL INSTRUCTIONS MUST BE...

Page 4: ...oltages causing problems such as excessive heat build up Because the harmonic waveforms contain higher order frequencies capacitive leakage currents may increase to above prescribed limits and shorten...

Page 5: ...from the load equipment or sub distribution point back to the point of entry and perhaps to the supply transformer the type of distribution system should be identifiable with the aid of the following...

Page 6: ...o this PE conductor Figure 4 TN C S system In this system a separate neutral and protective earth functions combine in a single PEN conductor This system is also known as a Multiple Earthed MEN system...

Page 7: ...om country to country it is important to ensure that the installation complies with all regulations applicable to the location Please seek further assistance if uncertain Regulations differ between co...

Page 8: ...abling and upstream over current protection requirements and all instructions provided in this manual should be taken into consideration before mounting the SRF To preserve the IP rating SRF units fro...

Page 9: ...on the external side surface of the enclosure The cabling and earth wires connected to the filter input should always be run separately with a minimum clearance of 300mm between them and all other cab...

Page 10: ...lock 25 to 120 mm2 19 N m Backplane Stud 1 x M8 8 5 N m 500A Stud Terminal Block 1 x M10 30 N m Backplane Stud 1 x M10 17 N m 800A Stud Terminal Block 2 x M10 30 N m Backplane Stud 1 x M10 17 N m SING...

Page 11: ...nVent com ERICO 11 SRF163N SRF3500N 2X CABLE TIE HOLES ON BACK PLANE TO FASTEN EARTH CABLE IN POSITION OUTPUT INPUT 6 2 CABLING Figure 9 Typical earth cabling Installation and Operating Instructions...

Page 12: ...one A similar scenario exists where the output of the SRF is fed to an electrically noisy load Any transients developed by this load may also be fed to other equipment connected to the same supply Ele...

Page 13: ...by the earthing system to which it is connected A low impedance route to the earth is required less than 10 This can be achieved by ensuring that the earth electrode system at the site presents a low...

Page 14: ...away from the input circuit and any other current carrying conductors Alarm contact ratings 5A 250VAC 54 30 VDC 4kV Isolation See section 7 Servicing and Trouble Shooting for further information Unde...

Page 15: ...provide a separate earth electrode for the SRF subject to compliance with relevant wiring regulations particularly where the filter is to be installed on a sub circuit some distance from the existing...

Page 16: ...fuse should be obtained from nVent as soon as possible Note that the N E Spark Gap does not have an LED SECONDARY UNITS The Secondary Units are blue in colour and contain the secondary shunt diverter...

Page 17: ...UNIT PHASE 1 SRFSUAC UNIT SRF3500N SECONDARY UNIT FUSES N E SPARK GAP PHASE 1 SPARK GAP SECONDARY UNIT FUSE SRF163N GREEN STATUS INDICATING LED DIVERTER MODULE STATUS INDICATING FLAG ALARM CONTACTS O...

Page 18: ...model number These units are supplied without the proprietary enclosure and are intended to be mounted in a customer s provided switchboard SINGLE PHASE SRF MODELS FUSE SECONDARY UNIT SG PRIMARY DIVE...

Page 19: ...the top surface and the outputs on the bottom surface See Section 6 2 Cabling SRF Model Enclosure Size mm Mounting mm W H D X1 X2 Y1 Y2 Fastener Diameter Weight Kg SRF163N 400 300 200 360 470 260 370...

Page 20: ...ctive Lightning Protection System nVent ERICO SYSTEM 2000 Conventional Lightning Protection System 6 Protect Low Voltage Data Telecommunications Circuits 1 4 2 5 3 6 Capture the Lightning Strike Prote...

Reviews: