7.3.7 LANGUAGE
The NRG-DM is translated in to 11 languages. In this menu
you can choose to use the following languages for the
firmware: Czech, Dutch, English, Finnish, French, German,
Lithuanian, Norwegian, Polish, Russian or Swedish.
7.3.8 FACTORY RESET
If you need to reset all the settings to the factory settings,
you can use the factory reset.
7.3.9 INFORMATION
In the information section of the thermostat, you will
find information on how to contact us, on the measured
temperatures and calibration and on the software version
in the thermostat.
8 TROUBLE SHOOTING
In the event of damage or malfunction of one of the
temperature sensors, the heating output cuts off (fail safe)
and an error code is displayed.
Number
Error type
E0
Room failure. NRG-DM is defective. Please
replace the thermostat.
E1
Room sensor defective or short circuited.
Please replace the thermostat.
E2
Floor sensor defective or short circuited.
Please check or replace the external sensor *
E5
Internal overheating. Please inspect the
installation
Table 3
* The floor sensor may be replaced by a new one (product
reference = 1244-002952). In case of replacement of
the floor sensor by a new sensor (1244-002952), the
sensor selection needs to be performed and you need to
choose the NRG-Temp sensor in the list of sensors (see
7.3.6 Sensor
).