JBU-100-E
JBU-100-EP
JBU-100-L-E
JBU-100-L-EP
ENGLISH
PTB 09 ATEX 1061 U
II 2G Ex e (e mb) II
II 2D Ex tD (tD mbD) A21 IP66
IECEx PTB 09.0039U Ex e (e mb) II
Ex tD (tD mbD) A21 IP66
Rated voltage:
JBU-100-E(P): 480 Vac**
JBU-100-L-E(P): 254 Vac
Ambient temperature: JBU-100-E(P): -50°C to +56°C**
JBU-100-L-E(P): -40°C to +40°C
**: Special conditions for safe use may apply.
Ex em ll T *
* For system Temperature Code, see heating cable or design documentation
Rated voltage:
277 Vac
Ambient temperature: -40°C to +40°C
BR-Ex e II
BR-Ex em II
(Russia, Kazakhstan, Belarus)
For other countries contact your local Pentair representative.
For proper installation, follow carefully the installation instructions of the applicable
connection kits: C25-100, C25-21, C25-100-METAL or CCON25-100
Maximum pipe temperature:
Heater type
T
max
continuous
T
max
intermittent
T
max
power off
1000h cumulative
BTV
65°C
85°C
–
QTVR
110°C
110°C
–
XTV
120°C
250°C
–
KTV
150°C
250°C
–
VPL
See tables below
–
260°C
VPL: Maximum pipe temperature in dependence of heater type and voltage
Heater Type
T
max
pipe
Cable
208 Vac
230 Vac
254 Vac
277 Vac
5VPL2-CT
235°C
230°C
225°C
225°C
10VPL2-CT
220°C
210°C
200°C
195°C
15VPL2-CT
200°C
180°C
145°C
105°C
20VPL2-CT
150°C
150°C
Not allowed
Heater Type
T
max
pipe
Cable
385 Vac
400 Vac
480 Vac
5VPL4-CT
230°C
230°C
230°C
10VPL4-CT
215°C
215°C
205°C
15VPL4-CT
195°C
195°C
160°C
20VPL4-CT
150°C
150°C
150°C
Special conditions for safe use using ATEX or IECEx approvals:
For ambient temperatures >+40°C:
Use a power cable with continuous temperature resistance of m90°C.
Use a metallic power cable gland approved for use in hazardous areas
(for example GL-38-M25-METAL) and heating cable gland (C25-100-METAL).
TC RU C-BE.МЮ62.B.02853
1Ex e IIC
Ex tD A21 IP66
для L версии
1Ex e mb IIC
Ex tD mbD A21 IP66