SELF TEST FUNCTION 

This product comes with a built in self-test facility. Once given a permanent mains supply, the luminaire will automatically carry out a monthly 
functional check & an annual full duration test, in line with the testing procedures to BS 5266. 

 

Initial Test 

 

After receiving a permanent mains power supply, the luminaire will now charge for 24 hours before carrying out a 3 hour duration test. 

 

During this test the LED module will illuminate & the green LED indicator will go out. 

Monthly Function Test 

 

After installation the luminaire will carry out a 30 second function test. This will be selected randomly between day 15 to day 30 after 
installation so all self-test products do not go into test mode at the same time. 

 

During this test the LED module will illuminate & the green LED indicator will go out. 

 

This test will then be repeated every 30 days. 

Annual Duration Test 

 

After 11 monthly function tests, the luminaire will carry a duration test.. 

 

The test will last 3 hours. 

 

During this time the LED module will illuminate & the green LED indicator will go out. 

 

FAULT INDICATORS 

If during the self testing a fault is detected, these will be indicated as follows by the RED LED indicator:  

 

1 flash every 3 seconds – 

Fault with battery. Maybe a battery failure & requires changing, or not connected properly. 

 

2 flashes every 3 seconds 

– Fault with LED module. 

 

3 flashes every 3 seconds – 

Duration time not being met so batteries will need to be replaced. 

 

NOTES 

1. 

After completion of tests listed above the luminaire will repeat the process of 11 monthly function tests & 1 annual duration test. 

2. 

If there was a power outage before any of the tests, the luminaire will delay the test appropriately to ensure a minimum 24 hours charge 
is received. 

3. 

A fault indicator will continue until the fault is fixed. 

4. 

A reset of the mains supply will be required to get the fault to clear after it has been fixed. 

 

MANUAL TESTING 

As this is a self-test product this is NOT recommended. 
A manual test can still be initiated by isolating the permanent live supply (e.g. via a keyswitch) for as long as required to check function/duration 
BUT choosing to do this extra manual testing over and above the self-testing WILL affect lifetime of the batteries & may result  in them not 
meeting full rated life. 
This would void any warranty with NVC. 
For this use we would recommend our non-Self Test version of this product.  
 

TESTING LOG BOOK 

Luminaire Type:   ……………………………… 

Luminaire Location/No.: 

………………………………... 

 

 

 

Installed By: 

 

……………………………… 

Installed Date: 

 

………………………..................... 

 
Contact Details: 

………………………………………………………………………………………………………………………….. 

M ONTH

T EST

Signed

Date

Signed

Date

S igned

Date

Signed

Date

Signed

Date

1

FU NCTION AL

2

FU NCTION AL

3

FU NCTION AL

4

FU NCTION AL

5

FU NCTION AL

6

FU NCTION AL

7

FU NCTION AL

8

FU NCTION AL

9

FU NCTION AL

10

FU NCTION AL

11

FU NCTION AL

12

D ISC HA RGE

FIFTH YEAR

FIRST YEAR

SECOND YEAR

THIRD YEAR

FORTH YEAR

Reviews: