background image

 

Plant Installation Instructions 

 

Installation of the Treatment Tank (see tank drawing in appendix) 

Review permit / design conditions accordingly, and decide on an appropriate location for the tank(s) 
which is accessible to the home sewer outlet.  Excavate a site which is approximately 1’ larger than the 
tanks at a depth that will allow proper coverage of the system.  The building sewer outlet will determine 
the minimum depth of the plant.  Make sure you have a smooth level surface for the base of the unit. 
The tank must be placed on stone-free undisturbed soil or fill sand / pea gravel over stony soil (stones 
greater than 1/2 “diameter).  Place the treatment tank into the excavated site and double check for level.  
Carefully backfill around the unit, gently compacting the soil as well as possible, and leaving the inlet 
and outlet holes open for connections.  Connect the influent end to the building sewer outlet.  Connect 
the appropriate discharge to the effluent end of the plant.  Only 4” schedule 40 pipes or equivalent per 
code should enter and exit the unit until undisturbed soil is reached.  Inlet and outlet pipes should extend 
at least 3” into the system, with a baffle on inlet as well as (double-tee) baffle assembly on outlet.  
Carefully install treatment unit components (next section), then install electrical components in 
accordance with local electrical codes.  Fill the unit to the level of the effluent discharge.  One by one, 
turn on each electrical component and verify that there are no leaks, air or water, throughout the system.  
If a leak is detected, repair and retest.  After all required health department or electrical inspections are 
fulfilled, carefully backfill the excavated site.  The first 4” of backfill around and on top of the tank is to 
be the same as the backfill under the tank.  Visually inspect all above ground connections, and double 
check riser perforations for sign of misplaced boot seals, etc.  Connect the clarifier tee to the effluent 
pipe inside the unit making sure it is in the level vertical position.  Install riser vent or vented lid at the 
digester access riser, or as an alternative, vent at clarifier access if tank is properly constructed with free-
moving air between digester & clarifier.  

 

Installation of Components (see assembly drawing in appendix) 

Read the equipment parts list provided in the owner’s manual and verify that all required parts are on 
site.  Before the system package is installed inside of the unit, each component should be carefully 
inspected for damage or defects.  Never install damaged components inside of the treatment system.  
The dual port linear blower should be no more than 50’ away from the plant and in a well ventilated 
area.  The precaster will typically install a tank adapter ring onto the lid of the tank, which works well if 
there is 12” or more of riser height available to accommodate the blower.  If the tank is shallower, 
blower can be installed at remote location (either in separate ventilated basin or crawlspace, etc.).   
Air line to diffusers should be made with 1” PVC schedule 40 pipe.  Make sure the pipe is stable and 
resting on the excavated surface as opposed to hanging.  All PVC glue fittings should be connected 
using approved PVC primer and cement.  Use provided adapter fittings to adapt from blower to 1” PVC, 
as outlined in assembly drawing.  A hole saw will be necessary to tap through the riser(s), and rubber 
grommets (recommend pull thru Polylok grommets) will be necessary to keep riser perforations 
watertight.  As per the assembly diagram, the diffuser manifold assembly will hold the diffusers off the 
bottom of the tank approximately 4 inches.  The screw-in diffusers are placed parallel to and 
approximately 4” away from the inter-compartmental wall.  Verify that the clarifier tee assembly is 
vertical and level for correct operation.  The second aerator port marked “skimmer” will adapt to ½” 
Schedule 40 PVC as per the assembly diagram.  This line feeds the airlift for the sludge recirculation.  
The 1” PVC recirculation inlet is installed vertically in the inlet of the clarifier, 4” from the angled 
hopper floor as measured from the lowest measurable point.  Tie the ½” skimmer airline into the 1” x ½” 
tee exactly 8 inches above the recirculation inlet.  The recirculation line then runs vertically up to a point 
as shown on the tank diagram above the liquid level, and then runs horizontally back across the digester 
to the pretreatment tank.  Upon entering the pretreatment tank, immediately adapt up to 2” Schedule 40 
PVC with the provided adaptor (this is necessary to avoid splashing at the return inlet).  Then run the 2” 
PVC back to a point visible from the access riser above and into the 2” San-Tee provided.  Extend the 2” 
PVC down into the pretreatment tank as shown on the tank diagram.  The Aerator and alarm control 
panel should be installed in areas where their function will not be hindered.   

Summary of Contents for BNR 500 GPD

Page 1: ...ion Owners Manual Class I Wastewater Treatment Systems 500 550 600 800 1000 1500 Gallon per Day Capacity Commercial and Residential Systems The Environmentally Friendly Alternative for Wastewater Trea...

Page 2: ...e treatment area waste is continually exposed to microbes for the remainder of the treatment process The digestion action of the aerobic microbes results in a lower concentration of pathogenic bacteri...

Page 3: ...designed to set the right environment for aerobic microbes to grow by having air pumped in with a specific formation The air is diffused into microscopic bubbles by low pressure diffusers This proces...

Page 4: ...sandy soil freeof largeclumps of clay 5 Install rest of system affix risers toadapters w ith w aterproof adhesive 6 Performw atertightness test infieldas requiredby local jurisdiction 7 Uponapproval t...

Page 5: ...5...

Page 6: ...ner s manual and verify that all required parts are on site Before the system package is installed inside of the unit each component should be carefully inspected for damage or defects Never install d...

Page 7: ...nded in the form of a Pre Trash tank This tank should be one compartment and should be between 500 and 1000 gallons Inlet and outlet baffle tees are advisable Pre Trash Options A simple single compart...

Page 8: ...t or replaced Check for vibrations against solid structures Check filter cover for proper torque Maintenance Requirements Ongoing maintenance contracts are required for advanced treatment The installe...

Page 9: ...introduced periodically to function properly If circumstances occur where the unit will not be used for long periods of time bioremediation is recommended to seed the system before functional use begi...

Page 10: ...not required to register your warranty Representatives will be responsible for all warranty information If you wish to register your warranty please call ENVIRO FLO Inc directly and your information w...

Page 11: ...defective components or materials for loss incurred because of interruption of service or for any other special consequential damages or incidental expenses arising from the manufacture sale or use of...

Page 12: ...annual basis a continuing service policy to cover labor for normal inspection maintenance and repair According to state law all owners of aerobic systems must maintain a factory authorized service pr...

Reviews: