Installation Manual
Refit terminal cover before replacing the electrical panel.
4.0 ELECTRICAL INSTALLATION
Electrical work should be undertaken by a qualified electrician in
accordance with the wiring regulations.
18
21
19
20
22
23
Removing Electrical Panel
Refitting Terminal Cover
Removing Terminal Cover
Completing Connections
Wiring - On / Off Switch
Wiring - Integral Sensor
Release the electrical panel from the fan plate.
Remove the terminal cover.
Clamp the cable and complete the connections.
4.1 Electrical Consumption & Weights
Model
Input Power*
(W)
Weight
(kg)
Max.
Economy
XS6WA supply & extract
38
20
4.7
XS9WA supply & extract
50
37
6.5
XS12WA supply & extract
100
70
9.4
*Values are for extract only at 50hz.
4.3 Electrical Specification
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm maximum or minimum Fuse: 3 amp (if fan
is supplied from a 5A lighting circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled from
the same MFC speed control. This avoids the possibility of one fan (if
speed controlled at a lower flow rate) being stalled by the other fan(s).
Adequate make-up air provision sufficient to provide ventilation in
accordance with building regulations is required in all rooms. This
should be checked during commissioning with all fans in the same room
running together in all possible configurations.
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
4.4 Wiring diagrams
4.4.1 On / Off Switch Operation
IMPORTANT
Isolation - Before commencing work, make sure that the unit is
electrically isolated from the mains supply.
L5
L4
L3
L2
L1
N
or
L
N
Double pole
XS Fan unit
isolator
Fuse
max. 3 amp
Connect link wire between L2 & L4 for extract
or Connect link wire between L2 & L3 for supply.
Double pole
isolator
Fuse
max. 3 amp
L5
L4
L3
L2
L1
N
or
L
N
XS Fan unit with
integral sensor
SL
(Switched Live)
Connect link wire between L2 & L4 for extract
or Connect link wire between L2 & L3 for supply.
Connect switched live signal to L5 for integral timer module.
4.4.2 Integral Sensor Operation