NuAire XS12WA Installation Manual Download Page 5

5

18. 03. 20. Document Number  671051

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

XS WA

Installation Manual

Refit terminal cover before replacing the electrical panel.

4.0 ELECTRICAL INSTALLATION

Electrical work should be undertaken by a qualified electrician in 
accordance with the wiring regulations.

18 

21 

19 

20 

22 

23 

Removing Electrical Panel

Refitting Terminal Cover

Removing Terminal Cover

Completing Connections

Wiring - On / Off Switch

Wiring - Integral Sensor

Release the electrical panel from the fan plate.

Remove the terminal cover. 

Clamp the cable and complete the connections.

4.1 Electrical Consumption & Weights

Model

Input Power* 

(W)

Weight 

(kg)

Max.

Economy

XS6WA supply & extract

38

20

4.7

XS9WA supply & extract

50

37

6.5

XS12WA supply & extract

100

70

9.4

*Values are for extract only at 50hz.

4.3 Electrical Specification

230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by 
overload device. Cable: 1mm maximum or minimum Fuse: 3 amp (if fan 
is supplied from a 5A lighting circuit, no local fuse is required).

Note: If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same 
operating mode in the same room they should all be controlled from 
the same MFC speed control. This avoids the possibility of one fan (if 
speed controlled at a lower flow rate) being stalled by the other fan(s).

Adequate make-up air provision sufficient to provide ventilation in 
accordance with building regulations is required in all rooms. This 
should be checked during commissioning with all fans in the same room 
running together in all possible configurations.

The automatic shutters, motor bearings should be frequently inspected 
and maintained to ensure they open fully/operate satisfactorily. Use 
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse 
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362 
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.

Always confirm airflow direction before commissioning.

4.4 Wiring diagrams

4.4.1 On / Off Switch Operation

IMPORTANT

Isolation - Before commencing work, make sure that the unit is  

electrically isolated from the mains supply.

L5
L4
L3
L2
L1
N

or

L

N

Double pole

XS Fan unit

isolator

Fuse

max. 3 amp

Connect link wire between L2 & L4 for extract
or Connect link wire between L2 & L3 for supply.

Double pole

isolator

Fuse

max. 3 amp

L5
L4
L3
L2
L1
N

or

L

N

XS Fan unit with 

integral sensor

  SL

(Switched Live)

Connect link wire between L2 & L4 for extract
or Connect link wire between L2 & L3 for supply.
Connect switched live signal to L5 for integral timer module. 

4.4.2 Integral Sensor Operation

Summary of Contents for XS12WA

Page 1: ...by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or ot...

Page 2: ...rated via the optional XS MFC remote controller allowing supply or extract variable speed and automatic or manual switching of several fans if desired 2 2 Sensors Sensors are available as remote units...

Page 3: ...support the other end INSIDE OUTSIDE Install the sleeve at a slight angle lower to outside IMPORTANT When fitting the sleeve introduce a slight downward slope to the outside to encourage any water to...

Page 4: ...e Assembling Fan Release the electrical cover from the fan plate Bring the cable through the fan plate Assemble the fan plate to the inside sleeve IMPORTANT During shutter operation of XS fans there w...

Page 5: ...ed control This avoids the possibility of one fan if speed controlled at a lower flow rate being stalled by the other fan s Adequate make up air provision sufficient to provide ventilation in accordan...

Page 6: ...5 L4 L3 L2 L1 N L4 L3 L2 L1 N L1 N Double pole isolator Fuse max 3 amp L N XS Fan unit with integral sensor Required if using integral Timer mains supply Remote switch may be set On Off Forward Revers...

Page 7: ...ors Optional The XS MFC Multi Fan Control provides supply or extract variable speed and automatic or manual switching of several fans if desired see note below The control is best mounted approx 1 5m...

Page 8: ...the prepared wall 37 Mounting Backplate 5 0 ANCILLARIES 5 1 Weather Terminal Used for exposed site wall installations comprising one weather terminal manufactured from HIPS Order Code XS WT6 Dimensio...

Page 9: ...0 END OF LIFE AND RECYCLING Where possible Nuaire use components which can be largely recycled when the product reaches its end of life Fans motors controls actuators cabling and other electrical comp...

Page 10: ...10 18 03 20 Document Number 671051 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XS WA Installation Manual NOTES...

Page 11: ...11 18 03 20 Document Number 671051 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XS WA Installation Manual NOTES...

Page 12: ...12 18 03 20 Document Number 671051 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XS WA Installation Manual NOTES...