Installation Manual
4.0 ELECTRICAL INSTALLATION
The provision of the electrical supply and the connection of the
unit to the electrical supply must be carried out by a qualified
electrician in accordance with latest edition of the wiring
regulations.
All-pole disconnection from the mains as shown in the wiring
diagram must be incorporated within the fixed wiring and shall
have a minimum contact separation of 3mm in accordance with
latest edition of the wiring regulations.
22
Electrical Panel Installation - 1
Release the electrical panel from the fan plate.
23
Electrical Panel Installation - 2
Remove the terminal cover.
24
Electrical Panel Installation - 3
Clamp the cable and complete the connections.
25
Electrical Panel Installation - 4
Refit terminal cover before replacing the electrical panel.
4.1 Electrical Specification
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied
from a 5A lighting circuit, no local fuse is required).
If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled
from the same MFC speed control. This avoids the possibility of one
fan (if speed controlled at a lower flow rate) being stalled by the
other fan(s).
Adequate make-up air provision sufficient to provide ventilation in
accordance with building regulations is required in all rooms. This
should be checked during commissioning with all fans in the same room
running together in all possible configurations.
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
4.2 Electrical Information
Model
Input Power (W)*
Weight
(kg)
Max.
Economy
XS6FR
38
20
6.3
XS6PR
38
20
6.3
XS9FR
50
37
8.7
XS9PR
50
37
9.1
XS12FR
100
70
11.0
XS12PR
100
70
11.8
*Figures shown are for extract airflow only when electrical
frequency = 50Hz.
4.3 Shutter Operation
There will be a short delay on startup and shutdown of
approximately 40 seconds, this is normal.