Installation Manual
NOXMASTER - PIV with Carbon Filtration
5.0 ELECTRICAL CONNECTION
5.1 Electrical Details
Voltage:
230V 1ph 50Hz
IMPORTANT
The fan unit is also supplied with a fused spur. The three core
mains cable from the unit should be connected to a fixed
wiring installation, via the spur, in accordance with current IEE
wiring regulations.
5.2 Wiring Diagrams
5.2.1 NOXMASTER (All Versions Without Heater)
1A Fused Spur
(Supplied)
2 Pole Isolator
(By Others)
MAINS
230V
50Hz
N
L
Blue
Brown
Supply cord
from unit
Green/yellow
IMPORTANT
The electrical connection of the unit must be carried out by
a qualified electrician.
For good EMC engineering practice, the power supply output
cable and any sensor cables should not be placed within
50mm of other cables or each other.
4.3.3 Dual Inlets
The unit features a dual inlet which automatically selects the air source
based on the surrounding temperature. To utilise this feature, the
circular guard needs to be knocked out and the supplied spigot fitted
(ensure the lose guard is removed from the unit). If ducted air supply is
not being used,
do not knock out guard.
•
Fix the required spigot to the unit with the screws provided and
seal with silicone to eliminate air leakage.
•
Duct to the outside using ridged ducting.
Spigot
Guard - Punched
out and removed
150mm inlet
duct to outside
Soffit grille (Part No. 775229) fixes over rectangular
ducting which has been pulled through the rectangular
hole (220mm X 80mm) cut in soffit and folded flat up
against the surface of the soffit.
Note that a minimum soffit width of 130mm is required.
Form end of
rectangular ducting
to fit connector
and secure using
dynotie connector.
150mm dia.
insulated ducting
connected to unit
spigot using
dynotie connector
(Part No. FLDI150).
220mm x 90mm flexible
PVC Rectangular ducting
(Part No. PVC933WH).
Note: this duct should
be kept as short as
possible.
Circular duct connector
(Part No. RDC150).
150mm dia. insulated ducting
connected to unit spigot using
dynotie connector
(Part No. FLDI150).
150mm dia. pipe
(Part No. PVC130-6WH).
Insulated duct formed over pipe
and sealed with dynotie connector.
199 x 215 x 20mm
white plastic wall grille
(Part No. PVC604WH).
Figure 7. Fitting Dual Inlets
Figure 8. Soffit Installation
Figure 9. Wall Installation
Ceiling
Joist
Metal
Mounting
Bracket
A.V.
Mount
A.V.
Mount
Washer
3” Woodscrew
50mm
Min.
12mm
Clearance
Hole
Control Output
Time Clock (controls bypass damper)
Thermostat (controls intake damper)
Heater Output
Figure 4. Anti-Vibration Mount Installation
Figure 5. NOXMASTER-HEAT Installation
Figure 6. NOXMASTER-HEAT Installation