Installation Manual

Min 5

Drop

Condensate Trap Installation

Condensate pipe connection to 
unit and a typical example of a 
“U” trap drainpipe 

(Standard 

configuration only).

 

Collar

10 

MVHR-DRAIN Installation

Condensate drain, 
uninsulated drain pipe with 
min 5° fall running to SVP.

 
 

To SVP 

“T” piece 

MVHR Drain 

To unit 

To CONTRAP 

11 

"T" Piece CONTRAP & MVHR Drain Connection

When using a “T” Piece to connect the CONTRAP drainage and 
the MVHR drain pipework the MVHR drain must always be fitted 
before the “T” Piece to prevent condensate from feeding back into 

the MVHR system.

3.5 Extract / Input Areas

The unit is designed to extract air from all wet rooms e.g. bathroom, 
kitchen, en-suite, utility room (with sink).  WC’s do not need to be 
ventilated if openable windows are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and lounge. 
Extract / input grilles should be adjustable valve types (not supplied). 
External grilles are to have a minimum free area of 12,250 sq. mm.

3.6 Ducting

Before commencing ducting installation reference should be made 
to building regulations document “Domestic ventilation compliance 
guide”. This document supports ADF2010 and details installation, 
testing and commissioning of all ventilation systems.

It is recommended that rigid ducting be used at all times. Flexible 
ducting has a very high resistance and it is impossible to calculate how 
much resistance will be on a system if used.

If used the flexible ducting must be kept to a minimum and should 
always be pulled taut. A maximum of 300mm should be used on each 
leg.

To prevent condensation on the outside of the outside air inlet duct and 
the air outlet duct from the unit, these ducts should be insulated. 

Ducting must be installed in such a way that resistance to airflow is 
minimised. Bends should be kept to a minimum.

A minimum distance of 300mm between the appliance and any bends 
in ductwork is recommended.

Ideally 150mm diameter or 204 x 60mm rectangular ducting should be 
used (Figures 13 & 14).

Ducting joints must be sealed with silicone type sealant and shall be 
adequately and reliably fixed to the appliance.

3.7 Ventilation Flow Rates

ADF 2010 - Extract Ventilation Rates

Room

Minimum High rate

Minimum Low Rate

Kitchen

13 l/s

Total extract rate 

should be at least 

the whole dwelling 

ventilation rate given 

in table 2.

Utility Room

8 l/s

Bathroom

8 l/s

Sanitary 

Accommodation

6 l/s

 

Whole Dwelling Ventilation Rates 

Number Of Bedrooms In Dwelling

1

2

3

4

5

Whole dwelling 

ventilation rate 

(l/s)

1,2

13

17

21

25

29

Notes: 

1. In addition, the minimum ventilation rate should be no less than 0.3 

l/s per m² of internal floor area.  (This includes all floors, e.g. for a two-

story building add the ground and first floor areas).
2. This is based on two occupants in the main bedroom and a single 

occupant in all other bedrooms. This should be used as the default 

value. If a greater level of occupancy is expected add 4 l/s per occupant.

Any air intake terminal must be installed in accordance with the 
appropriate regulation. As a guide, the BS5440 series of British 
Standards deals with this issue and currently states that an air 
intake must be at a minimum distance of 300mm from a gas 
boiler balanced flue. Installers are advised to be aware of the 
requirements of this standard when installing ‘through the wall’ 
supply air ducting.

Summary of Contents for MRXBOXAB-ECO3-OHSW

Page 1: ... or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information Thi...

Page 2: ...e unit and building fabric 1 Airflow Through unit Standard Unit Extract air from house Intake air Exhaust air from outside to outside from house to house Supply air Intake air from outside Extract air from house Supply air to house Exhaust air from house to outside 2 Airflow Through OH unit Opposite Hand Unit Extract air from house Intake air Exhaust air from outside to outside from house to house...

Page 3: ...uld be positioned on a 25mm minimum thickness MDF panel that is vertically fixed across the roof trusses to form a solid false wall Add additional vertical supports if necessary Use the Anti vibration tray assembly MRXBOX AV 3 5 including the angle brackets to be purchased separately 8 Angled Brackets Loft Mounted Installation 3 3 Off Site Cupboard Construction For off site constructed cupboards a...

Page 4: ...led taut A maximum of 300mm should be used on each leg To prevent condensation on the outside of the outside air inlet duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended I...

Page 5: ... as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in ADF 2010 Extract Ventilation Rates table The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further ...

Page 6: ... Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulated extract duct 3 10 2 Rectangular Ducting 14 Typical Rectangular Ducting Arrangement For Wall Mounted Units Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air from outside via air brick All duct betwe...

Page 7: ...connected to the underside of the MVHR unit within The cable should be fed through rubber blanking plug to provide a seal when the cover is re fitted 4 3 Wiring Diagrams 4 3 1 Unit Serving Kitchen And Bathroom 16 Wiring Diagram Unit Serving Kitchen And Bathroom ECO3 3A Fuse BS 1362 ECO5 5A Fuse BS 1362 MAINS 230V 50Hz Light Room Light Switch Double Pole N L 3 Pole Isolator Kitchen Switch Blue Brow...

Page 8: ... to solely boost the unit Additional switch should be used local to the wet rooms Section 4 3 3 5 2 Status Indication The status of the unit is indicated by a series of LED s on the front cover The variants are listed below The display on the unit control panel will not indicate when a higher speed setting has been triggered by an external source such as an ES PIR2 etc 20 Unit Control On Front Pan...

Page 9: ...ulations and guidelines taking into account all site based risks 9 0 AFTER SALES AND REPLACEMENT PARTS For technical assistance or further product information including spare parts and replacement components please contact the After Sales Department If ordering spares please quote the serial number of the unit together with the part number if the part number is not known please give a full descrip...

Page 10: ...10 28 07 21 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 SC SW Installation Manual NOTES ...

Page 11: ...11 28 07 21 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 SC SW Installation Manual NOTES ...

Page 12: ...12 28 07 21 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 SC SW Installation Manual NOTES ...

Reviews: