NuAire MRXBOX95-LOFT Installation And Maintenance Manual Download Page 6

6

14. 02. 14. Leaflet Number 671438

Installation and Maintenance

MRXBOX95-LOFT Mechanical Ventilation with Heat Recovery

Optional Connections

Ecosmart control 

(see figure 6).

(a) J11/12/13

The IDC plug-in connectors are provided for the connection of

compatible sensors. 

NOTE: Do not run the data cable in the same conduit as the

mains cable and leave a 50mm separation with any power

cables.

(b) Volt Free Relay Contacts 

Note that the volt free contacts are not fused. If these are used

to power any external equipment, the installer must provide

adequate fusing or other protections. These contacts are rated

at 5A resistive, 0.5A inductive.

Run connections (J5)

- These contacts are closed when the

fan is running.

Fault connections (J7)

- No fault = the contacts are closed.

Fault

= the contacts are opened (this includes no power supply

at the unit).

(c) Data Cable installation

A 4-core data cable is used to connect devices such as sensors

to the fan and for interconnecting multiple fan units.

Do not run data cable in the same conduit as the mains cables

and ensure there is a 50mm separation between the data cable

and other cables. The maximum cable run between any two

devices is 300m when it is installed in accordance with the

instructions.

Please note that the total data cable length used in any system

must be less than 1000m. Keep the number of cable joints to a

minimum to ensure the best data transmission efficiency

between devices.

LED Indication

PWR GREEN: 

Power on and OK,

RED: 

Standby LED on when fan is not running. 

As the unit runs continuously this LED should 

be off. If it is illuminated locate the trickle 

switch and change its position.

Fan 1 GREEN:

Fan 1 is running, 

RED:

Fan 1 faulty.

Fan 2 GREEN: 

Fan 2 is running, 

RED:

Fan 2 faulty.

Electrical connection cont.

Summary of Contents for MRXBOX95-LOFT

Page 1: ...of the unit see figures 2a 2b and 2c for fixing details Lower the unit with the L shape fixing brackets attached onto the joists Mark through the brackets and drill four clearance holes into the top...

Page 2: ...move any burr and file if necessary to remove any external sharp edges Mark the socket depth on the pipe and check that the pipe section to be jointed is free of any surface damage which may affect th...

Page 3: ...ce MRXBOX95 LOFT Mechanical Ventilation with Heat Recovery Figure 4 Typical MVHR ducted arrangement for a loft mounted unit using the Nuaire condensation trap 125mm dia CONTRAP 125 2 3 Extract input a...

Page 4: ...FROM TOP Condensate Drain 21 5mm dia condensate drain 21 5mm dia condensate drain alternative position SIDE VIEW controls 3 0 Dimensions mm Figure 6 Figure 5 Main unit components shown with front and...

Page 5: ...bles or switched live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables 4 0 Electrical Connection Please note the electrical connection of the uni...

Page 6: ...re opened this includes no power supply at the unit c Data Cable installation A 4 core data cable is used to connect devices such as sensors to the fan and for interconnecting multiple fan units Do no...

Page 7: ...0 Maintenance Cleaning Please allow 300mm each side of the unit to allow access for maintenance purposes 1 Replace filters every 5 years Remove the top cover and slide out the two G4 filters fitted e...

Page 8: ...affected 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be arrang...

Reviews: