background image

2

nuaire.co.uk 

029 2085 8400

30. 05. 19. Document Number  671924

Installation and Maintenance

MEV-X

 - Continuous Extract Unit

4.0 DIMENSIONS (mm)

4.1 Unit Dimensions 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The unit is not fitted with a back-draught shutter or filter as 
standard. These should be integrated into the system design where 
appropriate and can be purchased from Nuaire if required.  If 
extracting from a dwelling it is advised the incoming air to the unit 
is filtered to minimum grade of G2.  

It is recommended that rigid ducting be used it all times. Flexible 
ducting has a very high resistance and it is impossible to calculate how 
much resistance will be on a system if used.

If used, the flexible ducting must be kept to a minimum and should 
always be pulled taut. A maximum of 300mm should be used on each 
leg.

If used to supply fresh air from outside the heated envelope of the 
dwelling, the duct should be insulated with material having a thermal 
resistance of >0.625m2 K/w, in order to prevent condensation on the 
exterior of the duct to the unit.

Ducting must be installed in such a way that resistance to airflow is 
minimised. Bends should be kept to a minimum.

A minimum distance of 200mm between the appliance and any bends 
in ductwork is recommended. Ideally 200mm diameter or 220 x 90mm 
rectangular ducting should be used.

Ducting joints must be sealed with silicone type sealant and shall be 
adequately and reliably fixed to the appliance. 

3.2 Pre-Commissioning 

The unit must not be used during site construction or the clean-up 
period as cement and plaster dust can be abrasive which may affect fan 
performance and reliability. 

While the property is drying out, very high moisture levels are likely 
to occur. Therefore it is advisable that if the installation and building 
works are complete the unit is left running. If the building works are not 
complete, please close or cover the air valves to prevent condensation 
forming in the ductwork and unit due to natural migration of warm air.

Airflow

151

150

70

81

590

560

131

230

303

20

220

230

10

25

165

40

35

Mains Entry (Allow 20mm Clearance)

Figure 1. Unit Dimensions

3.0 INSTALLATION

The provision of the electrical supply and the connection of the unit 
to the mains must be carried out by a qualified electrician.  All-pole 
disconnection from the mains as shown in the wiring diagram must be 
incorporated within the fixed wiring and shall have a minimum contact 
separation of 3mm in accordance with latest edition of the wiring 
regulations. Ensure that the mains supply (Voltage, Frequency and 
Phase) complies with the rating label.

Please note sufficient access and a clear working space around 
the unit is required to allow access for commissioning and also 
for maintenance of key components, please allow a minimum of 
110mm from the access panels (Figure 1). An additional 20mm will 
be required at the mains entry point to allow cable routing, this 
distance will be greater if using an additional cable gland.

The unit is designed to be installed predominantly on a ceiling/slab, 
the unit must not be floor mounted.  If wall mounting to prevent 
potential water ingress the cable entry should be on the underside 
of the unit or replaced with a sealed cable gland, the unit must also 
be mounted square to prevent ingress around the PCB cover. 

The unit must be installed indoors, on a suitable wall away from direct 
sources of frost, heat and water spray or moisture generation. For a 
vibration-free result the unit must be mounted to a solid structure.

 The unit can be secured in place using the four mounting holes (fixings 
supplied by others) provided (Figure 2).

To ensure vibration is not transferred into the structure, it is 
advised to fit a small spacer (supplied) between the unit and the 
mounting surface at each fixing point.

3.1 Ducting

Ducting must be securely fixed with screws to the spigot to prevent 
access to live parts. Duct runs terminating close to the fan must be 
adequately protected by suitable guards.

Precautions must be taken to avoid the back-flow of gases into the 
room from the open flue of gas or other fuel-burning appliances.

Reviews: