Installation and Maintenance
MEV-X
- Continuous Extract Unit
5.0 ELECTRICAL CONNECTION
All electrical connections must be carried out by a qualified electrician.
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
If wall mounting to prevent potential water ingress the cable entry
should be on the underside of the unit or replaced with a sealed cable
gland, the unit must also be mounted square to prevent ingress around
the PCB cover.
The supply cord should be run so the lowest point is below the cable
entry grommet to prevent water ingress.
5.1 Examples of Typical Wiring Layouts
The below are examples of potential wiring layouts, alternatives
are possible and may be required depending on the installation
requirements.
Electrical details:-
Voltage: 230V 1ph 50Hz
Consumption: 1.1 A
Note: The unit must be earthed.
The cable from the mains power supply should be connected to a fixed
wiring installation via a fused isolator in accordance with current wiring
regulations.
IMPORTANT
For good EMC practice, any sensor cable or switched live
cables should not be placed within 50mm of, or on, the same
metal cable tray as other cables.
O Y W B
L
L
SL
SUPPLY
WARNING
HIGH VOLTAGE
651616 A0
FAN
CTRL
N
1 2
Speed 2
230 V
Mains
Connection
Motor
Connections
Speed 3
N
SP1
SP2
SP3
IMPORTANT
All-pole disconnection from the mains as shown in the wiring
diagram must be incorporated within the fixed wiring and shall
have a minimum contact separation of 3mm in accordance
with latest edition of the wiring regulations.
Figure 3. PCB
5.2 Mounting Hole Dimensions
136
269
Ø6.6
272
538
Figure 2. Mounting Hole Dimensions