For good EMC engineering practice, any sensor cables
or switched live cables should not be
placed within 50mm of other cables or on the same
metal cable tray as other cables.
The unit is normally designed to ventilate the property
continuously to give between 0.5 and 0.7 air changes
per hour.
A facility is included which boosts the duty as required.
The boost can be achieved by the following methods:
a) Switched Live (SL)
Connection of 230V mains to SL terminal.
b) Optional Remote Speed Control (OPUS-SPD)
The speed control will mimic the speed between the max
and min settings selected at the fan. Connect OPUS-SPD
to LV terminal.
c) Internal Humidistat (on the ES-MEV-H unit only)
The internal humidistat can be found on the base of the
fan case. The adjustment dial gives a range of 50 - 80%
@ 20
0
C. (See figure 8). Setting to mid position gives 65%
which should be acceptable for most circumstances.
N
L
SL
Do not use
To OPUS-SPD
speed control
Internal
humidity adj.
To remote
fail indicator
ES-MEV-AVI
Calibration
Status
30
0
60
Run-on
(mins)
50
10
90
Max
Airflow
(l/s)
50
10
90
Min
Airflow
(l/s)
LVT NET TR
3
Leaflet Number 671266 July 2007
Fuse 2A
Unit serving Kitchen and Bathroom
MAINS
230V
50Hz
Room
light
Light
switch
(Double
Pole)
U
N
L
SL
N
L
Fan
Unit
F
3 Pole
isolator
3
Fuse 2A
Unit serving Bathroom only
MAINS
230V
50Hz
Optional
lamp
N
L
SL
N
L
Fan
Unit
3 Pole
isolator
Remote/light switch
Kitchen switch
4.0 Electrical Wiring (basic)
4.1 Electrical Wiring (options)
Unit serving Kitchen and two Bathrooms
N
Fuse 2A
MAINS
230V
50Hz
Room
lights
Light
switches
(Double
Pole)
N
L
SL
N
L
Fan
Unit
3
3 Pole
isolator
Kitchen switch
Figure 6.
Figure 7. Circuit Board Connections.
Installation and Maintenance
MEV Ecosmart Continuous Mechanical Extract Ventilation Units
All field wiring, switches and isolators, by others.