NuAire Ecosmart MRXBOX95-WM2-1Z Installation And Maintenance Manual Download Page 7

Isolation - Before commencing work make sure that the 

unit, switched live and Nuaire control are electrically 

isolated from the mains supply and switched live supply. 

6.0 Commissioning

All infomation on this page is specific to the MVHR unit fitted
inside the enclosure, the front panel of the enclosure must be
removed to gain access.

2/

For the required air flow rates please refer to the design 
specification for the property, follow 2.4, or refer to building 
regulations ADF 2010.

3/

The unit is supplied with independent control for both normal 
and boost airflows. (see fig. 14). 

4/

Correct commissioning is essential to ensure the ventilation air 
flowrates are met. It also ensures the unit is not over ventilating 
and causing excessive power consumption. 

5/

Commissioning should be carried out in accordance with building 
regulations document “Domestic ventilation compliance guide”. 

www.planningportal.gov.uk/building regulations/approved 
documents/partf/associated.

 

A calibrated moving vane 

anemometer and hood will be required to carry out 
commissioning.

6/

Adjustment valves should be locked in place to prevent further 
adjustment. 

7/

Once commissioned the home owner / tenant should be 
informed that the unit should not be adjusted as it will have a 
detrimental effect on the indoor air quality and could result in 
condensation and mould growth. The label covering the control 
has an adhesive panel which should be removed post 
commissioning to prevent tampering.

8/

Speed 1 is limited to never exceed speed 2, when commissioning 
the speed 2 should always be set first. 

6.1 Speed 3

The  unit  has  the  ability  to  override  both  speed  1  and  speed  2  to 
operate the fan to maximum airflow. See wiring diagram for details of 
operating this facility.

6.2 Humidity adjustment 

(AB unit only).

This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the

 

humidity exceeds the set point the unit will boost to that set by the

 

commissioned boost speed. The set point can be found on the front 
of

 

the unit (see Fig. 14) and is at its least sensitive when turned fully

 

clockwise. Note that the sensor is measuring humidity from all the

 

wet rooms at the same time and should not be relied on to solely

 

boost the unit. Additional switch should be used local to the wet

 

rooms (see wiring diagrams).

7.0 Status Indication

The status of the unit is indicated by a series of LED’s on the front
cover. The varients are listed below.

8.0 Thermal Bypass (Non AB models)

In the event of excessive outside temperatures, and to help prevent
over-heating, the supply fan will automatically reduce to a trickle
speed. Under these circumstances additional ventilation measures may
be required e.g. open windows or trickle vents (if fitted).

9.0 Maintenance/Cleaning

We recommend that the two G3 fiters are inspected after 6 months,
and replaced every 12 to 18 months. The filters can be removed from
the unit by removing the two filter covers on the front panel of the
unit. Take hold of the two circular tabs either end of the filter covers
and pull out.

The filter can now be extracted by pulling the removal loop on the
front edge of the filter. Once the filters have been inspected return
or replace them as necessary. Inspect the heat exchanger every 
5 years. Generally check for damage and security of components.
Refit cover.

7

27. 11. 17. Leaflet Number 671722

Installation and Maintenance

The WM2 Wall Mounted Range of Units

Filter

Filter cover

Outer enclosure cover

MVHR unit cover

Heat exchanger

Heat exchanger

Figure 15. Removing the two filter covers on the front panel of the
unit. The filters can be removed by pulling on the black tab on the
visible end of the filters. 

Figure 14. Detail of unit control
on front panel.

(Standard configuration only).

Humidity 
adjustment.

(AB unit only).

The filters fitted inside the unit are protected with a 

plastic film. Prior to commissioning remove the covers 

(fig 15), take off the film and replace.

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

060923

HX Bypass

(AB units only)

Speed 

2

Speed 

1

Speed 

2

Speed 

1

Summary of Contents for Ecosmart MRXBOX95-WM2-1Z

Page 1: ...all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase com...

Page 2: ...d the cover plate slid along the length to bond against the base panel of the enclosure preventing noise breakout fig 7 Figure 7 1 The condensate must be discharged under a water level in a U trap dra...

Page 3: ...t duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum...

Page 4: ...sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least...

Page 5: ...ply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling...

Page 6: ...on to Remote Fail Indicator Ref MRXBOX95 RFI Optional 3 2 Figure 11a Note Wiring is for reference purposes only as the connections in fig 11a are factory fitted The unit is pre wired with a 2 metre fl...

Page 7: ...st to that set by the commissioned boost speed The set point can be found on the front of the unit see Fig 14 and is at its least sensitive when turned fully clockwise Note that the sensor is measurin...

Page 8: ...rranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified...

Reviews: