NuAire Ecosmart MRXBOX95-WM2-1Z Installation And Maintenance Manual Download Page 3

3

27. 11. 17. Leaflet Number 671722

Installation and Maintenance

The WM2 Wall Mounted Range of Units

2.4 Extract/input areas

The unit is designed to extract air from all wet rooms e.g. bathroom,
kitchen, en-suite, utility room (with sink). 
WC’s do not need to be ventilated if openable windows are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and lounge.
Extract / input grilles should be adjustable valve types (not supplied).
External grilles to have a minimum free area of 12,250 sq mm.

2.5 Ducting

Before commencing ducting installation reference should be made to
building regulations document “Domestic ventilation compliance
guide”. This document supports ADF2010 and details installation,
testing and commissioning of all ventilation systems.

If the enclosure is to be used in conjunction with an ancillary 
distribution box (DB-WM2) refer to additional assembly instructions
supplied with the DB-WM2 as requirements will differ.

Otherwise fit 4x 150mm diameter plastic spigots with the self 
tapping screws supplied to the spigot fixings plates found on the top
panel of the enclosure, a bead of silicone should be applied to the
groove of spigot fixing plate to prevent leakage. (see fig. 3)

It is recommended that rigid ducting be used at all times. 
Flexible ducting has a very high resistance and it is impossible to 
calculate how much resistance will be on a system if used.

If used the flexible ducting must be kept to a minimum and should
always be pulled taut. A maximum of 300mm should be used on each
leg.

To prevent condensation on the outside of the outside air inlet duct
and the air outlet duct from the unit, these ducts should be 
insulated. 

Ducting must be installed in such a way that resistance to airflow is
minimised. Bends should be kept to a minimum.

A minimum distance of 300mm between the appliance and any
bends in ductwork is recommended.

Ideally 150mm diameter or 220 x 90mm rectangular ducting should
be used. (Refer to dwelling design drawing, figure 10a and 10b on
page 5 for further information).

Ducting joints must be sealed with silicone type sealant and shall be
adequately and reliably fixed to the appliance.

2.6 Ventilation flow rates

Table 1.

ADF 2010  – Extract ventilation rates

Room

Min high rate

Min low rate

Kitchen

13 l/s

Utility room

8 l/s

Bathroom

8 l/s

Sanitary 
accommodation

6 l/s

Table 2.

Whole dwelling ventilation rates

Number of bedrooms in dwelling

1

2

3

4

5

Whole

13

17

21

25

29

dwelling 
ventilation 
rate l/s

1, 2

Notes:

1,

In addition, the minimum ventilation rate be should be not less

than 0.3 l/s per m

2

of internal floor area. 

(This includes all floors, e.g. for a two-story building add the
ground and first floor areas).

2,

This is based on two occupants in the main bedroom and a 

single occupant in all other bedrooms. This should be used as the
default value. If a greater level of occupancy is expected add 4 l/s
per occupant.

Total extract rate should be
at least the whole dwelling
ventilation rate given in
table 2.

Any air intake terminal MUST be installed in accordance with the 
appropriate regulation.

As a guide, the BS5440 series of British Standards deals with this issue

 

and currently states that an air intake must be at a minimum distance of

 

300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this standard

 

when installing ‘through the wall’ supply air ducting.

Summary of Contents for Ecosmart MRXBOX95-WM2-1Z

Page 1: ...all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase com...

Page 2: ...d the cover plate slid along the length to bond against the base panel of the enclosure preventing noise breakout fig 7 Figure 7 1 The condensate must be discharged under a water level in a U trap dra...

Page 3: ...t duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum...

Page 4: ...sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least...

Page 5: ...ply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling...

Page 6: ...on to Remote Fail Indicator Ref MRXBOX95 RFI Optional 3 2 Figure 11a Note Wiring is for reference purposes only as the connections in fig 11a are factory fitted The unit is pre wired with a 2 metre fl...

Page 7: ...st to that set by the commissioned boost speed The set point can be found on the front of the unit see Fig 14 and is at its least sensitive when turned fully clockwise Note that the sensor is measurin...

Page 8: ...rranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified...

Reviews: