NuAire Ecosmart MRXBOX95-WM2-1Z Installation And Maintenance Manual Download Page 6

6

27. 11. 17. Leaflet Number 671722

Installation and Maintenance

The WM2 Wall Mounted Range of Units

For good EMC engineering practice, any sensor cables or

switched live cables should not be placed within 50mm of

other cables or on the same metal cable tray as other cables.

5.0  Electrical Connection

Please note: the electrical connection of the unit must be be carried
out by a qualified electrician.

The unit is supplied with a flexible cord for connection to the mains
supply.

Electrical details:-

Voltage:

 

240V  1ph  50Hz

Consumption:  1.3 Amp 

Fuse rating: 

3 Amp

NOTE This unit must be earthed.

The cable from the mains power supply should be connected 

to a fixed wiring installation, via a fused isolator, in

 

accordance with current IEE wiring regulations.

Fuse 2A

MAINS
230V
50Hz

Room
light

Light 

switch 

(Double 

Pole)

N

L

3 Pole
isolator

Kitchen switch

Blue

Brown

Black

Optional s

peed 3 

switch

Supply cord
from unit

Grey

Green/yellow

Unit serving kitchen and bathroom

Figure 12. 

Unit serving kitchen and two bathrooms

Figure 13. 

SWL2     L 

   SWL1 

  L 

  N

C

N

7

 E

X

T

R

A

C

T

C

N

6

 S

U

P

P

LY

BLU

WHI

YEL

RED

SUPPL

Y

BYP

ASS

SUPPLY F

AN

EXTRACT F

AN

B

L

U

B

R

N

B

R

N

B

L

U

EXTRACT F

AN

B

L

U

B

R

N

EXTERNAL PUMP

BLU

WHI

YELI

RED

 F

A

IL

CN8

TH1    

TH2

L         N

CN5

Connection to Remote Fail 
Indicator Ref: MRXBOX95-RFI

 

(Optional)

3

2

Figure 11a.

Note: Wiring is for reference 
purposes only as the connections
in fig. 11a are factory fitted. 
The unit is pre-wired with a 
2 metre fly lead. 

Disconnection from the
supply mains must be
incorporated within the
fixed wiring in accordance
with the wiring regulations
and shall have a minimum
contact separation 
of 3mm.

Disconnection from the
supply mains must be
incorporated within the
fixed wiring in accordance
with the wiring regulations
and shall have a minimum
contact separation 
of 3mm.

Figure 11b. If an Ecosmart device is to be connected

the removable cover found next to the power cable

exit on the base panel of the enclosure should be

removed by loosening the two screws, the Ecosmart

cable can then be connected to the underside of the

MVHR unit within (fig 11b).  The cable should be fed

through rubber blanking plug to provide a seal when

the cover is re-fitted.

Connector for
Ecosmart devices 

Power Cable 

Fuse 2A

MAINS
230V
50Hz

Room
lights

Light 

switches 

(Double 

Pole)

N

L

3 Pole
isolator

Kitchen switch

Green/yellow

Blue

Brown

Black

Supply cord
from unit

Optional s

peed 3 

switch

Grey

5.1  Optional Controls 

For further information contact Nuaire on 029 2085 8400.

If more than one Ecosmart sensor is required

 

please  use  MRXBOX-JB  and  refer  to  leaflet

 

No. 671700 for installation instructions.

Supply    Supply    Extract    Extract

Speed1   Speed2    Speed1    Speed2

Summary of Contents for Ecosmart MRXBOX95-WM2-1Z

Page 1: ...all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase com...

Page 2: ...d the cover plate slid along the length to bond against the base panel of the enclosure preventing noise breakout fig 7 Figure 7 1 The condensate must be discharged under a water level in a U trap dra...

Page 3: ...t duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum...

Page 4: ...sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least...

Page 5: ...ply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling...

Page 6: ...on to Remote Fail Indicator Ref MRXBOX95 RFI Optional 3 2 Figure 11a Note Wiring is for reference purposes only as the connections in fig 11a are factory fitted The unit is pre wired with a 2 metre fl...

Page 7: ...st to that set by the commissioned boost speed The set point can be found on the front of the unit see Fig 14 and is at its least sensitive when turned fully clockwise Note that the sensor is measurin...

Page 8: ...rranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified...

Reviews: