background image

Reversal of the BMS connection will damage the control.

4

Installation, Operating and Maintenance Instructions

DAVE Supply Fans (ES Models) 50/60Hz

5

.0 Wiring

Wiring Connections for units with Ecosmart Control

a) Mains connections.

Mains cables should be suitably sized and terminated at terminals
shown on the appropriate diagram.

b) Control Connections.

Below: ‘Net’ connection for Ecosmart devices.

Net - the 4 IDC plug-in connectors are provided for the connection
of compatible sensors, manual controls and for linking the fans
together under a common control. If more than 4 connections are
required, the junction box (product code ES-JB) should be used 
(see data cable installation).

c) Switched Live (SL) terminal. 

A signal of 100-230V

 / 220V

 a.c. will activate the fan from 

either its off state or trickle state (see setting to work-trickle 
switch).

 

When the SL is disconnected the fan will over-run 

(see setting to work-timer adjustment).
Do not take this signal from an isolating transformer.

d) Volt Free Relay Contacts.

LED indication 

for units with Ecosmart Control

PWR

GREEN: Power on & OK. RED: To much power 
is taken by peripherals or there is a short circuit in 
the net cable. Check the cable and use a junction box 
(ES-JB) to connect some of the peripherals.

Standby

LED on when fan is not running.

Fan 1

GREEN: Fan 1 is running, RED: Fan 1 faulty.

Fan 2

GREEN: Fan 2 is running, RED: Fan 2 faulty. (Twinfan only)

Heating* Not applicable. See note.
Cooling* Not applicable. See note.
Fault

LED on when a fault is present on unit.

Frost*

Applicable with LPHW only. See note.

Tx

LED on when the controller is transmitting data.

Rx

LED on when the controller is receiving data.

* Note that the control panel is common to all the Ecosmart
products and will have indicators for functions that are not
available in this particular fan. However these indicators will
not be illuminated.

e) Commissioning panel details. 

Note: A Commissioning Procedure document (leaflet No. 671153) 
is available on request from Nuaire Tel: 029 2088 5911.

The Control Module 

Fig 12: 

The BMS connection is made with a plug-in connector 

via the socket (See figure 13). To ensure the connection 

is made only by suitably qualified and authorised 

personnel the plug is not supplied. 

It is available from R S Components, 
Part No. 403-875 or Farnell, Part No. 963-021.

The system’s response to a 0-10V dc BMS signal is given below.

Note the BMS signal will override any sensors and user control
connected in the system. The voltage tolerance is +/_ 125mV and
is measured at the fans terminal.

Ventilation 

Cooling 

Heating 

mode

mode*

mode*

Local control

0.00

-

-

OFF / trickle

0.25

-

-

Speed 1

0.50

0.75

1.00

Speed 2

1.50

1.75

2.00

Speed 3

2.50

2.75

3.00

Speed 4

3.50

3.75

4.00

Speed 5

4.50

4.75

5.00

Speed 6

5.50

5.75

6.00

Speed 7

6.50

6.75

7.00

Speed 8

7.50

7.75

8.00

Speed 9

8.50

8.75

9.00

Speed 10

9.50

9.75

10.00

* Only available on relevant unit

 

Volt Free 
Contact  
RUN signal

5A resistive
0.5A inductive

Volt Free 
Contact  
FAULT signal

R

UN      F

A

UL
T

N

L

SL

DP

CL

N

RET

 

230V 50Hz 1ph / 220V 60Hz 1ph 

Remove this link wire 
ifa switched live signal is 
connected to terminal SL
NOTE: Also remove link 
if a BMS is connected.
Also remove link if an 
enabling device is 
connected in the 'NET'

Switch live signal
(if required)

NET connections for 
ECOSMART devices

No user 
connections

CO2 sensor

connections

0  
+ve signal
from BMS

ECOSMAR

T NET

Ribbon cable
to commissioning
box

  Fault signal

Remove link if switched live signal,
an enabler or BMS signal is connected.

Terminals or PCB

Mains connection pre-wired

 

230V 50Hz 1

ph / 220V 60Hz 1ph 

N

E

L

SL

  Fault signal

LED indicators

Min 

Max 

SL run on

Trickle

Test

0        

1

Pwr

Standby

Fan 1 

Fan 2 

Heating

Cooling

Fault

Frost

Tx

Rx

 

MIN 

=  Minimum speed
 

adjustment

MAX 

=  Maximum speed
 

adjustment

SL Run on  =  Switched Live Run-On

 

Timer adjustment

TRICKLE 

=  Selects trickle running:
 

0 = off, 1 = selected

TEST 

=  Test button

Fig 8: 

Fig 9: 

Fig 11: 

RUN 

FAULT

Run signal    Fault signal

Fig 10: 

Fig 13: 

18. 10. 17. Leaflet Number 671679

Summary of Contents for DAVE Series

Page 1: ... are manufactured from aluzinc rectangular in section and have circular rigid spigots at each end All units are supplied with fixing brackets designed to simplify installation 1 0 Fan Unit Coding Descriptions 2 0 Handling Always handle the units carefully to avoid damage and distortion Care must be taken to ensure any slings used for hoisting do not damage the casing or the control module componen...

Page 2: ...5 190 DS3A EES H 1005 780 345 200 430 155 155 DS4A NES H 1005 840 370 250 370 150 100 DS4A LES H 1005 840 370 250 430 175 190 DS4A EES H 1005 840 370 250 430 155 155 DS4HA NES H 1005 840 370 250 370 150 100 DS4HA LES H 1005 840 370 250 430 175 190 DS4HA EES H 1005 840 370 250 430 155 155 DS5A NES H 1155 1110 1110 984 410 315 370 150 100 DS5A LES H 1155 984 410 315 430 175 190 DS5A EES H 1155 984 4...

Page 3: ...valve to a fully open position to allow full water flow through the coil and the main PCB will close the Heat demand contacts These contacts could be used to send a signal to activate the boiler and or valve to open to provide heat if not already doing so 4 1 2 Port Pressure Independent Balancing Control Valve Setting Instruction Fig 6 Remove Actuator Fig 7 Unlock Adjusting Collar Units 1 2 2H DN2...

Page 4: ...el details Note A Commissioning Procedure document leaflet No 671153 is available on request from Nuaire Tel 029 2088 5911 The Control Module Fig 12 The BMS connection is made with a plug in connector via the socket See figure 13 To ensure the connection is made only by suitably qualified and authorised personnel the plug is not supplied It is available from R S Components Part No 403 875 or Farne...

Page 5: ...ater Neutral Thermistor T Thermistor R Signal 0V Signal VE OIP 5V Note Customer connections for electric heater 40amp draw E N L L N E Heater Temperature Settings Note Customer connections for fan and control 5amp draw max 5 18 10 17 Leaflet Number 671679 Notes Local isolator by others All inter connections between circuit boards blowers and sensors are made at the factory Remove link wire if swit...

Page 6: ...OL COOLING CONTROL 0V SETPOINT 0 10V 10V 0V DEADBAND 0 10V 10V AUTO HEAT COOL OFF ON COOL SENSOR ACTUATOR CONTROL WHITE ACTUATOR CONTROL BLACK ACTUATOR CONTROL RED Note Customer connections for fan and control 5amp draw max 6 18 10 17 Leaflet Number 671679 Notes Local isolator by others All inter connections between circuit boards blowers and sensors are made at the factory Remove link wire if swi...

Page 7: ...nce Ensure all control components are secure and clean refit the cover Lubrication Motors are fitted with sealed for life bearings and do not require any lubrication Filter care replacement The filter where applicable will require cleaning on a regular basis The frequency of the cleaning operation will depend on the site conditions 7 0 Fan Components see fig 18 Key Components A Lid Base B Attenuat...

Page 8: ...es office for further details 9 0 Spares for Dave Supply fans Spare parts and replacement components are available from Nuaire Ltd Please contact us on the numbers below for further details G4 Filter Unit Size Replacement Part No DS1A ES D1A G4FILTERKIT DS2A ES D2A G4FILTERKIT DS2HA ES D2HA G4FILTERKIT DS3A ES D3A G4FILTERKIT DS4A ES D3A G4FILTERKIT DS4HA ES D4HA G4FILTERKIT DS5A ES D5A G4FILTERKI...

Page 9: ...nged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orientation 4 2 Where installation accessories...

Reviews: