NuAire CYFAN-C Installation And Maintenance Manual Download Page 4

CYFAN-C EXTRACT FANS 

INSTALLATION AND MAINTENANCE

24V fan units must be installed in accordance with these 

instructions and IEE Wiring Regulations BS7671 

for SELV installations.

For good EMC engineering practice, any sensor 

cables or switched live cables should not be placed within 50mm 

of other cables or on the same metal cable tray 

as other cables.

4

10. 05. 17. Leaflet Number 691500

2.3 Conversion from 230V to 24V cont.

5.

Separate section 2 of the PCB from section 1 by cutting the tabs
in the positions shown. (see fig 4). Replace section 2 of the PCB
into the fan unit.

Fig 4. Separate section 1 of the PCB (Power supply 230V/24V) from
section 2 (Control PCB 24V DC) by cutting the tabs in the positions
shown with the dotted circles.

Fig 5. Section 1 of PCB will be installed into the transformer 
enclosure after the 24V wiring has been completed.

2.4 Installation of Transformer Enclosure
(24 Volt units only)

The enclosure containing the transformer is intended to be mounted
out of sight (e.g. in a loft, cupboard, under floorboards etc.).
However, if this is not possible the transformer enclosure should be
mounted as close to the ceiling, or as far from the "splash zone" as
possible (see below for definition of the splash zone). 
As can be seen from the table of wiring sizes, it is advisable to place
the enclosure as close to the fan as possible to reduce the costs of
wiring and assist in installation.

‘Splash zone’

The ‘Splash Zone’ can be considered to be an area within a bathroom
or shower room where a person using the bath or shower can 
effectively reach. 
An arms reach is defined as 0.6 metres from the edge of the bath or
shower up to a height of 2.25 metres.

2.5 Procedure for fitting the Transformer

1. Remove the transformer cover.

2. Position the transformer base enclosure on mounting surface and

route cables through knockouts. Mark the fixing points on the
mounting surface. Secure using suitable fixings (by others).

3. Before fitting section 1 of the  PCB into the transformer

enclosure connect wiring as shown in (24V wiring options). 
Fit section 1 of the PCB by first slotting the bottom edge 
(see fig 6) into the fixing clip inside the base of the transformer 
enclosure then press on the transformer and terminal block until 
the PCB clicks into place. Complete by replacing the transformer 
cover using the screws provided. 

4. Keep vents clear of obstruction.

Complete the installation of components by securing the PCB
cover on the fan.

Note: No earth is to be connected between transformer and fan.

Fig 6. Place section 1 of the PCB into the transformer enclosure 
supplied with the fan. 

2.6 Transformer installation notes for
wiring sizes

It is important to note that the size of wire used between the 
transformer and the fan unit can have an adverse effect on the 
units performance if the following table is not adhere to.

Mains Supply: (230V)

0.5mm sq.

Transformer to fan (24V units only)
Cable run (max. 10 metres)

Cable size

Up to 2m

0.75 mm sq.

Up to 4m

1.0 mm sq.

Up to 6m

1.5 mm sq.

Up to 10m

2.5 mm sq.

SECTION 2.0 
UNIT PREPARATION CONT.

Section 2 (Control PCB 24V DC)

Motor 
connection

24V SELV
output

24V SELV
input

Connection
to pull-cord

SL  N   L

T

Transformer

S

0

2

SL

0

24V

24V

0

SL

Mains supply
terminal block

Section 1 
(Power supply 
230V to 24V)

Section 1 (Power supply 230V to 24V)

Mains supply

24V SELV
output

SL  N   L

Transformer

Terminal block

Bottom edge of PCB.

SL

0

24V

Terminal block

Place section 1 of PCB
into the transfomer enclosure

Top fixing clip

Slot for small flat screwdriver to come from 
underneath the transformer to push clip to one side

Note to installing electrician: To avoid cable insulation contact with
hot transformer, always use the knockout at PCB end.

Summary of Contents for CYFAN-C

Page 1: ...rate toilet Part number CYFAN DKIT n Semi recessed mounting kit Part number CYFAN RKIT n Optional filter available Part number 7702017 1 4 What comes in the box The following components are included S...

Page 2: ...o 24V conversion n All Wiring Diagrams Section 3 Fitting the Product Page 6 Section 4 Setting the Product to work Page 12 n Default settings n Part F Flow rates n Air flow adjustment Inc Controls labe...

Page 3: ...e simple steps to fit your back draught shutters if required It is advised to fit the shutters before installing the fan unit n Collect all required parts n 125mm shutters 2 off 41285 or 100mm shutter...

Page 4: ...osition the transformer base enclosure on mounting surface and route cables through knockouts Mark the fixing points on the mounting surface Secure using suitable fixings by others 3 Before fitting se...

Page 5: ...if not fitted fan will run at full speed only 24V 0 SL Fan unit Section 2 PCB Transformer Box Fan unit Section 2 PCB 2 Pole switch Fuse 2A BS 1362 N L Mains 230V 50Hz Wiring for two room installation...

Page 6: ...n spigot placed into core cut hole and use the base as a template to mark the mounting screw hole positions x3 remove casing once marks are made 8 Drill and plug if necessary the mounting surface 9 Fe...

Page 7: ...ed wiring flex through the back of the fan casing and mounting plate 11 Secure the case to the surface fixings supplied by others Note care must be taken not to twist or distort the case whilst fittin...

Page 8: ...replace PCB fully into position by pushing the dip switches 10 Replace PCB cover by fitting with 2 off No6 x 1 2 inch screws see point 2 of the procedure Fig 17 Use cable clamp on rear of casing to s...

Page 9: ...osses in the outer assembly draw the inner and outer assemblies together Remove any tape supporting the outer assembly and continue to draw the units together until the O ring is compressed on the win...

Page 10: ...lter f Reduction Filter Fig 22 Example of a subsidiary spigot kit Code CYFAN DKIT Note 50mm grille available Code 50IG 2 Place the front cover to one side 3 Place the reduction filter over the grille...

Page 11: ...tting 13 Partially replace PCB into the new fan casing and wire flex into the terminal block see wiring options on page 5 Go to point 19 14 Utilizing the fan skirt Using the template on page 12 mark o...

Page 12: ...K Relative Intermittent Intermittent Humidity Boost Set at 60l s Boost Set at 30l s 60 20 l s 10 l s 70 30 l s 15 l s 80 40 l s 20 l s 90 50 l s 25 l s 100 60 l s 30 l s Fan Failure Boost Humidity Fan...

Reviews: