05. 11. 20. Leaflet Number 671829
BOXER BPS
ECOSMART ADAPT (TREND) CONTROL (AT)
17
7.0 DESCRIPTION OF CONTROL - SOFTWARE STRATEGY
7.18 SETPOINTS (CONTINUED)
Most of the following are user adjustable within engineered limits:
Knob
No.
Name
Description
Range
Default
20
High Air Temp Alarm
High supply air temp alarm temperature
30-70 °C
50 °C
21
Low Air Temp Alarm
Low supply air temp alarm temperature
-40-20°C
8 °C
22
Heating Type 1=LPHW 2=Electric
Heating Type 0=None, 1=LPHW, 2=Electric
0-2
0
23
Cooling Type 1=CW 2=DX 3=RC
Cooling Type 0=None, 1=CW, 2=DX, 3=Reverse Cycle
0-3
0
24
Summer Night Free Cool MinTemp Night cooling lower cut-off temperature
5-30°C
10°C
25
SummerNight Free Cool FanSpeed Night cool fan speed
20-100%
80%
29
Supply Fan Start Voltage
The voltage threshold of passing 0% rotational speed
0-5 v
1 v
30
Extract Fan Start Voltage
The voltage threshold of passing 0% rotational speed
0-5 v
1 v
31
Supply Fan Voltage Limit
The maximum voltage to be supplied to the fan motor
6-10 v
10 v
32
Extract Fan Voltage Limit
The maximum voltage to be supplied to the fan motor
6-10 v
10 v
41
CP Loop Gain
Constant Pressure Loop Gain
0-50
0.5
42
IO Damper Delay
Delay to allow inlet outlet dampers to open
0-300 sec
0 sec
43
Boost Run-on
Boost Run On
0-3600 sec
0 sec
44
CP Loop Integral
Constant Pressure Loop Integral
0-30
1
45
CP Loop Derivative
Constant Pressure Loop Derivative
0-30
0
46
FrostProTemp
Temperature, below which, any water valves will be overridden open
-40-10°C
4 °C
47
Constant Pressure Setpoint
Setpoint for constant pressure mode
0-1000 Pa
400 Pa
50
MinFrostProtectPeriod
Minimum time frost protection will be enabled
0-600 sec
300 sec
51
Recirc Offset
The temperture difference require before recirculation starts
0-20°C
5 °C
58
Cool Loop Gain
Cool Loop Gain
-30-0
-5
59
Cool Loop Integral
Cool Loop Integral
0-30
2
60
Cool Loop Derivative
Cool Loop Derivative
0-30
0
61
Heat Loop Gain
Heat Loop Gain
-30-0
-5
62
Heat Loop Integral
Heat Loop Integral
0-30
2
63
Heat Loop Derivative
Heat Loop Derivative
0-30
0
64
CO2 Loop Gain
CO2 Loop Gain
-30-0
-0.5
65
CO2 Loop Integral
CO2 Loop Integral
0-30
10
66
CO2 Loop Derivative
CO2 Loop Derivative
0-30
0
Summary of Contents for B815H/ER/AT-L
Page 25: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 25 Figure 10...
Page 27: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 27 Figure 11...
Page 29: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 29 Figure 12...
Page 31: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 31 Figure 13...
Page 33: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 33 Figure 14...
Page 35: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 35 Figure 15...
Page 37: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 37 Figure 16...
Page 39: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 39 Figure 17...
Page 41: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 41 Figure 18...
Page 43: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 43 Figure 19...
Page 45: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 45 Figure 20...
Page 47: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 47 Figure 21...
Page 49: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 49 Figure 22...
Page 51: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 51 Figure 23...
Page 53: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 53 Figure 24...