Installation and Maintenance

AXUS Swift Circular Long Cased Axial Flow Fans

4.0 Electrical Wiring

4.1 Single Phase Units 

4.2 Three Phase Units 

Single Speed, 1 phase

D.O.L. Starting, 3 phase (3kW and below)

Single Speed, 3 phase

Speed Control - TRANSFORMER, 1 phase

Speed Control - ELECTRONIC, 3 phase

Star / Delta Starter, 3 phase (4kW and above)

IMPORTANT

For specialist connections not shown always refer 

to the wiring diagram supplied with the unit. In 

the event of query or uncertainty contact NUAIRE 

directly before any connection is made.

X      L     N  

Fan
Unit

NOTE:
Remove Link between
 X+L when using 
speed control

L  N

230V 1 phase 50Hz supply
220V 1 phase 60Hz supply

N  

L    

 X     

Fan
unit

L      N

230V 1 phase 50Hz supply only  

L1

N    L2    N    N     

  L    

Control
SPCON

460V 3 phase 60Hz supply  

380V 3 phase 60Hz supply  

400V 3 phase 50Hz supply  

L1

L2

L3

STAR

L1  -  U1

L2  -  V1

L3  -  W1
Link W2, U2, V2

U1

V1

W1

W2

U2

V2

 L1   L2   L3 

400V  3 phase 50Hz supply
380V  3 phase 60Hz supply

460V  3 phase 60Hz supply

Fan
unit

U1

V1

W1

W2

U2

V2

DELTA

L1  -  U1  -  W2
L2  -   V1  -  U2 
L3  -  W1  -  V2

Note: 
For all D.O.L. (Direct On Line)
operation or Inverter type Speed Control
wire in DELTA

460V 3 phase 60Hz supply  

380V 3 phase 60Hz supply  

400V 3 phase 50Hz supply  

L1     L2      L3

L1  

PE/  

N/L3  

  L/L2  

  W  

  U

  V  

400V 3 phase 50Hz supply  
380V 3 phase 60Hz supply  
460V 3 phase 60Hz supply  

3 Phase only
INVERTER SPEED CONTROL

Connections

to motor

3 Phase input

Motor

3 Phase

Notes:
Total Length of motor leads should not exceed 50 metres.
If a screened motor cable is used, maximum length should
be 25 metres. Consult our Technical Department if you 
wish to use longer leads.
Inverters are configured to suit specific fans and control
applictions as described on the Customer Order
free of charge.

Summary of Contents for AXUS SWIFT Series

Page 1: ...lso be referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating...

Page 2: ...35 C up to 85 relative humidity The controller must be fitted to a vertical vibration free wall with appropriate fasteners and for ease of installation the cover should be removed and the casing separ...

Page 3: ...L Control SPCON 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 L3 STAR L1 U1 L2 V1 L3 W1 Link W2 U2 V2 U1 V1 W1 W2 U2 V2 L1 L2 L3 400V 3 phase 50Hz supply 380V 3 phas...

Page 4: ...kle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5...

Page 5: ...creened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensur...

Page 6: ...sired airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire betwe...

Page 7: ...UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales...

Reviews: