Installation and Maintenance

AXUS Swift Circular Long Cased Axial Flow Fans

Figure 3. Resilient Mounting 
‘Floor’ fixing.

Figure 4. Resilient Mounting 
‘Suspended’ fixing.

Supporting 
foot.

Shakeproof 
washers.

Fixings by 
installer.

Supporting 
foot

25mm dia 
essential safety 
washer for 
suspended 
applications (four 
25mm washers 
supplied with 
kit), other fixings 
by installer.

Drop rods 
(by others).

Nuts used 
for height 
adjustment.

IMPORTANT

AV mounts isolate the fan only. Silencers / 

backdraught dampers and other "significant mass" 
accessories should form part of the fixed ductwork 

 after the flexible connection.

IMPORTANT

For good EMC engineering practice, any sensor cables 

or switched live cables should not be placed within 

50mm of other cables or on the same metal cable tray 

as other cables.

IMPORTANT

An inverter is used to provide speed control. When the 

fan is isolated, allow 5 minutes for the capacitors in the 

inverter to discharge before commencing any work on 

the unit.

3.3 Suspended Horizontally or Vertically

A.V. mountings must be arranged so that they are used in compression 
only. If Resilient Mountings NAV1 to NAV5 are specified the rubber 
mountings must also remain in compression. The large metal washers 
must be fitted under the studding nuts on each mounting (fig. 4).

Other types of A.V. mounts - spring etc. are also designed to be 
used in compression only.

A suspended steel underframe would be necessary to support the unit, 
(by others) standing on A.V. mountings.

3.4 Ecosmart Control Installation (optional)

The controller must be fitted indoors (an optional outdoor cover can be 
purchased) and away from water spray and heat source.

The operating range is -10°C to 35°C up to 85% relative humidity. 
The controller must be fitted to a vertical vibration free wall with 
appropriate fasteners and for ease of installation the cover should be 
removed and the casing separated from the base. If cooling fans are 
fitted they should be disconnected while installation takes place.

The cable connecting the Ecosmart control and the fan must be a 
screened power cable, not exceeding 30 metres.

The screening must be earthed at both ends using the special cable 
glands supplied.

Bridge any break in the screening 

(e.g. at local isolators) 

using braided 

earthing strap.

(Details of Ecosmart controls and wiring connections can be found 
on pages 4, 5 and 6).

3.5 Electrical Installation

Units are not supplied with electrical isolators, their selection and 
provision is the responsibility of the installer.

Ensure the electrical supply is suitable for the fan and that all wiring, 
fuse and overload protection, etc. is appropriately sized by comparing 
with the rating plate.

Electrical connection is made direct to the motor termination box on 
all fans, if explosion proof motors are fitted they will require matched 
specified wiring; refer to data sheet 671216 for additional advice.

Wiring connection diagrams; where a starter, frequency inverter 
or Ecosmart control is used also refer to the relevant control I&M 
instructions. Bifurcated fans should only be speed controlled by a 
frequency inverter.

It is essential to note that for all three phase fans of 4kW and above the 
final connection must be in DELTA.

If a Star/Delta starter is to be used, connect all six motor terminals 
to the appropriate terminals of the starter. If the fan is to be started 
direct on line (DOL) to a frequency inverter or Nuaire’s Ecosmart speed 
control the motor 

must be connected in Delta.

If T1/ T2 are located in the fan terminal block, this is the motor overheat 
protection device which is Thermistors or Thermostat as specified.

Summary of Contents for AXUS SWIFT Series

Page 1: ...lso be referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating...

Page 2: ...35 C up to 85 relative humidity The controller must be fitted to a vertical vibration free wall with appropriate fasteners and for ease of installation the cover should be removed and the casing separ...

Page 3: ...L Control SPCON 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 L3 STAR L1 U1 L2 V1 L3 W1 Link W2 U2 V2 U1 V1 W1 W2 U2 V2 L1 L2 L3 400V 3 phase 50Hz supply 380V 3 phas...

Page 4: ...kle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5...

Page 5: ...creened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensur...

Page 6: ...sired airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire betwe...

Page 7: ...UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales...

Reviews: