nuaire.co.uk 

029 2085 8400

08. 11. 17. Leaflet Number  671645

The EMC Directive

 

2014/30/EU

The Low Voltage 
Directive

2014/35/EU

AXS

AXUS Swift Circular Long Cased Axial Flow Fans

 

Installation and Maintenance

1.0 Introduction

The AXUS SWIFT range of axial flow fans are designed for ‘in duct’ 
applications. Manufactured from galvanised steel, the units are 
suitable for indoor or outdoor installation and at any installed 
angle.

Available for single and three phase supplies. 
Case diameters of 350mm to 1000mm. 
Unit codes AXS350 to AXS1000.

Impellers have been selected at blade angle settings matched to 
various motor speeds to perform against the design criteria laid down 
in our selection catalogue.

Any attempt to adjust or reset impeller blade angles will invalidate 
warranty.

For full unit description, dimensional, weight and performance details 
refer to the Nuaire product catalogue. A comprehensive range of 
ancillaries and silencers are also listed.

3.0 Installation And General Advice

Installation must be carried out by competent personnel, in accordance 
with good industry practice, the appropriate authority and in 
conformance with all statutory and governing regulations e.g. IEE, 
CIBSE, HVCA, ATEX, BSI & EN standards etc.

If the fan is to be installed in a potentially explosive atmosphere it will 
have been designed to ATEX directive 2014/34/EU and will incorporate 
motors requiring compatible installation wiring direct to the motor 
termination box, to complete this installation also follow the guidance 
advice of data sheet 671216.

Before commencing installation 

check that all materials, including 

optional ancillaries are available to complete the installation. Every unit 
is tested and serialised at works and a test certificate produced, the 
details recorded on the fan side rating plate should also be referred to 
before handling and installation.

Any damages or deviations should be immediately reported to the 
seller/supplier/agent quoting the order and product details from 
the product rating plate.

2.0 Handling

The fan impeller is carefully balanced and centralised in the fan case, 
it is therefore essential that great care is exercised when handling the 
unit. Check the weight on the rating plate details before attempting to 
lift and always use a spreader as shown (fig. 1), never pass lifting slings 
through the impeller (fig. 2).

3.1 Mechanical Installation

Rotate the fan impeller by hand to ensure free and smooth rotation and 
that no transit or handling damage has occurred, observe the direction 
of flow/direction of rotation arrow 

and ensure that:

All optional accessories such as support brackets, attenuators, 
inlet cones, guards, flexible connectors etc. are assembled to 
the fan.

The optional support brackets are correctly fitted, at any 
position around the circumference, but suit the installation 
plane.

External termination box is accessible to the electrician.

When offering the fan to the ducted system that both inlet 
and outlet connections are perfectly aligned.

In order to ensure performance is as stated, a minimum 
distance of twice the fan diameter is required between the 
appliance and any bends in the ductwork.

Figure 1. Correct method of 
lifting using a spreader.

Figure 2. The wrong method of 
lifting with sling through impeller 
can cause case distortion.

3.2 Horizontal on Floor or Supported from Wall etc.

Optional resilient mountings should be attached to the unit mounting 
brackets at this stage (fig. 3). If the unit is supported from a wall, 
supporting brackets should be used. Position and align the unit with the 
ductwork in both horizontal and vertical planes and pack height under 
mounting feet if necessary.

Matching attenuators if required; should be fitted to the fan with any 
other accessories before installation.

Matching flanges are fixed to the ductwork ends with rivets.

Summary of Contents for AXUS SWIFT Series

Page 1: ...lso be referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating...

Page 2: ...35 C up to 85 relative humidity The controller must be fitted to a vertical vibration free wall with appropriate fasteners and for ease of installation the cover should be removed and the casing separ...

Page 3: ...L Control SPCON 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 L3 STAR L1 U1 L2 V1 L3 W1 Link W2 U2 V2 U1 V1 W1 W2 U2 V2 L1 L2 L3 400V 3 phase 50Hz supply 380V 3 phas...

Page 4: ...kle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5...

Page 5: ...creened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensur...

Page 6: ...sired airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire betwe...

Page 7: ...UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales...