LPXBOXDC-2 Mechanical Ventilation with Heat Recovery

Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and 

dimensions of equipment and the right is reserved to make such changes without prior notice.

11.0 Connection of Drain Pipe

The unit needs a drain pipe to function correctly.

Remove the lid via the screws and decide which side the

drain pipe is to be connected. On the same side as where

the drain pipe is to be connected, fit a 135 degree elbow to

the copper pipe and connect a 22mm dia. plastic pipe to the

other side of the elbow and through the supplied “O” ring in

the outer wall. This is the drain pipe.

Seal the internal perimeter between the drain pipe and “O”

ring with silicone to prevent air leakage.

On the other copper pipe place the end stop as shown in 

the diagram below and place the supplied rubber bung into 

the opposite hole in the outer casing to prevent air leakage.

Replace the lid and hand tighten all the fixing screws.

22mm dia. 

Plastic Pipe

(by others)

135  Elbow

o

End Stop

22mm dia. 

Plastic Pipe

(by others)

135  Elbow

o

End Stop

Figure 8. Drain pipe configuration options.