Nuaire Group LPXBOXDC-2 Installation And Maintenance Manual Download Page 2

Any air intake terminal MUST be installed in accordance

with the appropriate regulation. 

As a guide, the BS5440 series of British Standards

deals with this issue and currently states that an air

intake must be at a minimum distance of 300mm from a

gas boiler balanced flue. Installers are advised to be

aware of the requirements of this standard when

installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be 

at least 300mm apart.

2

Leaflet Number 671390 July 2011

Installation and Maintenance

LPXBOXDC-2 Mechanical Ventilation with Heat Recovery

Side view (view from B) 

 

 

 

 

End view (view from A)

297 

 

        553

Plan view (view from underside 
with covers removed)

Plan view (Mounting bracket)

Plan view (view from top 
with covers removed)

106  

 

598

623  

 

140

97

66 

14

0

 

333 

View B

View A

General view of unit

2.0 Dimensions 

Figure 5. Dimensions in mm.

1

1

3

2

4

1

1

4

Key

Extract 

- stale air ducted from within ‘Wet’ rooms 

in the building.

Discharge 

- is the extracted air from the building 

ducted to the outside and removed.

Supply 

- is the fresh air ducted into the building. 

This may be sent to more than one room.

Intake 

- is the fresh air source ducted from outside.

1

2

3

4