PO Series Technical Specification
Page C.14
B
BB
BB
URNER
URNER
URNER
URNER
URNER
S
S
S
S
S
EQUENCE
EQUENCE
EQUENCE
EQUENCE
EQUENCE
C
C
C
C
C
ONTROLLER
ONTROLLER
ONTROLLER
ONTROLLER
ONTROLLER
: L
: L
: L
: L
: L
ANDIS
ANDIS
ANDIS
ANDIS
ANDIS
& S
& S
& S
& S
& S
TTTTTAEF
AEF
AEF
AEF
AEFA
AA
AA
L
L
L
L
LAL2.25
AL2.25
AL2.25
AL2.25
AL2.25
Enlarged Detail Of Sequence Indicator
Sequence
Indicator
P
1
I
In the event of a fault condition the sequence
disc stops rotating, with the symbol appearing
above the indicator mark indicating the nature
of the fault.
If the fault leads to a lockout condition the
orange lockout indicator will be illuminated.
Symbol Lockout
Fault
No
No
Yes
Yes
No
None
Yes
Yes
Yes
1
Failure of one or more of the pre-start checks. Before allowing the
sequence to begin the unit carries out the following checks:
Burner Controller not in lockout position.
Air Damper Closed (proved by limit switch supplying voltage from terminal
11 to terminal 8).
Fuel Valves closed (proved by limit switch supplying voltage to terminal 12)
Fuel pressure switch, Limit Thermostat or Limit Pressure Switch all closed
(proved by continuity between terminals 4 and 5)
Interruption to sequence whilst controller waits for the air damper to drive to
open position (proved by servo motor limit switch).
Lockout caused by the failure of the air pressure switch to changeover from
the 'no air' position shortly after the pre-purge.
Lockout caused by a fault in the flame supervision circuit.
Interruption to sequence whilst controller waits for the air damper to
drive to start position (proved by servo motor limit switch).
Lockout during the pre-ignition period not marked by a symbol is
usually caused by premature flame signal.
Lockout caused by the absence of a flame signal at the end of the first safety
period (time for start flame establishment).
Lockout caused by the loss of the flame signal during normal operation.
Summary of Contents for PO160
Page 5: ...Page B 1 PO Series General Information GENERAL INFORMATION ...
Page 14: ...Page B 9 PO Series General Information ...
Page 15: ...PO Series General Information Page B 10 AAD PFinal B_Gen PO B_Gen pmd 250504A ...
Page 16: ...Page C 1 PO Series Technical Specification TECHNICAL SPECIFICATION ...
Page 34: ...Page C 19 PO Series Technical Specification ...
Page 35: ...PO Series Technical Specification Page C 20 AAD PFinal C_Tech Po RWF40 C_Tech pmd 250504A ...
Page 36: ...Page D 1 P Series Commissioning COMMISSIONING ...
Page 42: ...Page D 7 P Series Commissioning ...
Page 44: ...Page D 9 P Series Commissioning AAD PFinal C_Tech Po RWF40 D_Comm pmd 250504A ...
Page 45: ...P Series Page 10 ...
Page 46: ...Page E 1 PO Series Operation And Maintenance E OPERATION AND MAINTENANCE ...
Page 51: ...PO Series Operation And Maintenance Page E 6 ...
Page 52: ...Page E 7 PO Series Operation And Maintenance ...
Page 53: ...PO Series Operation And Maintenance Page E 8 N N N N NOTES OTES OTES OTES OTES ...
Page 54: ...Page E 9 PO Series Operation And Maintenance N N N N NOTES OTES OTES OTES OTES ...
Page 55: ...PO Series Operation And Maintenance Page E 10 N N N N NOTES OTES OTES OTES OTES ...