Nu-Air Ventilation Systems Inc. - HRV Operating & Installation Manual
Rev. 2.3 Aug. 19, 2014
- 4 -
VENTILATION PERFORMANCE
ENERGY PERFORMANCE
EXT.
STATIC
NET SUPPLY
GROSS AIR FLOW
SUPPLY
NET
POWER
SENSIBLE
APPARENT
PRESSURE
AIR FLOW
SUPPLY
EXHAUST
TEMP.
AIR FLOW
CONSUMED
RECOVERY
SENSIBLE
in wg (Pa)
cfm (l/s)
cfm (l/s)
cfm (l/s)
ºF (ºC)
cfm (l/s)
Watts
EFFICIENCY
EFFECTIVENESS
0.1 (25)
143 (67)
144 (68)
174 (82)
+32 (0)
64 (30)
50
71
80
0.2 (50)
124 (58)
125 (59)
150 (71)
+32 (0)
96 (45)
80
64
73
0.3 (75)
109 (51)
110 (52)
135 (64)
+32 (0)
116 (55)
90
63
70
0.4 (100)
100 (47)
101 (48)
122 (58)
0.5 (125)
92 (43)
93 (44)
104 (49)
13 (-25)
60 (28)
69
64
82
0.6 (150)
78 (37)
79 (37)
93 (44)
0.7 (175)
63 (30)
64 (30)
86 (41)
0.8 (200)
46 (22)
47 (22)
72 (34)
MODEL: NU145
ELECTRICAL: 120V/1/60 Hz. 100W, 0.9A
This product earned the ENERGY STAR® by meeting strict energy efficiency guidelines set by Natural
Resources Canada and the US EPA. It meets ENERGY STAR requirements only when used in Canada.