Trinity Lx
│
Installation and Operation Instructions
Lx Series
70
Table 14-4 Alert Codes
Code
Description
Action/Response
54
Safety processor brown-out reset occurred
55
Application processor watchdog reset occurred
56
Application processor brown-out reset occurred
57
Safety processor watchdog reset occurred
58
Alarm was reset by the user at the control
59
Burner control firing rate was > absolute max rate
60
Burner control firing rate was < absolute min rate
61
Burner control firing rate was invalid, % vs. RPM
62
Burner control was firing with no fan request
63
Burner control rate (non-firing) was > absolute max rate
64
Burner control rate (non-firing) was < absolute min rate
65
Burner control rate (non-firing) was absent
66
Burner control rate (non-firing) was invalid, % vs. RPM
67
Fan off cycle rate was invalid, % vs. RPM
68
Set point was over ridden due to sensor fault
69
Modulation was over ridden due to sensor fault
70-74
RESERVED
75
Absolute max fan speed was out of range
76
Absolute min fan speed was out of range
77
Fan gain down was invalid
78
Fan gain up was invalid
79
Fan minimum duty cycle was invalid
80
Fan pulses per revolution was invalid
81
Fan PWM frequency was invalid
82-89
RESERVED
90
Modulation output type was invalid
91
Firing rate control parameter was invalid
92
Forced rate was out of range vs. min/max modulation
93
Forced rate was invalid, % vs. RPM
94
Slow start ramp value was invalid
95
Slow start degrees value was invalid
96
Slow start was ended due to outlet sensor fault
97
Slow start was end due to reference set point fault
98
CH max modulation rate was invalid, % vs. RPM
99
CH max modulation rate was > absolute max rate
100
CH modulation range (max minus min) was too small (< 4% or 40 RPM)
101
DHW max modulation rate was invalid, % vs. RPM
102
DHW max modulation rate was > absolute max rate
103
DHW modulation range (max minus min) was too small (< 4% or 40 RPM)
104
Min modulation rate was < absolute min rate
105
Min modulation rate was invalid, % vs. RPM
106
Manual rate was invalid, % vs. RPM
107
Slow start enabled, but forced rate was invalid
108
Analog output hysteresis was invalid
109
Analog modulation output type was invalid
110
IAS open rate differential was invalid
111
IAS open step rate was invalid
112
-114
RESERVED
115
Fan was limited to its minimum duty cycle