NTI E-ACLM-V/-P AC LINE MONITOR
10
To configure the spike threshold , click on “Voltage Spike Threshold”. Select the value to use from the dropdown. Options
include 50, 250, 500 and 1000 volts.
Figure 9- Configuration for Spike Thresholds
The E-ACLM-P provides additional configuration to control an internal relay that toggles power ON/OFF to the AC outlet. The
relay can be configured to disconnect power using one of four types of readings:
Figure 10- ACLM-P Spike Threshold and Relay Settings
Relay Settings include:
Feature
Description
Disconnect Type
Select the type of reading that will effect the operation of the relay (see below)
Disconnect
Place a checkmark to manually disconnect power through the relay (the Disconnect Type must be
set to "Manual")
Reconnect on normal
Select if the outlet should be powered ON when the reading has returned to the normal operating
range (provided the Disconnect Type isn’t set to "Manual")
Enable Min. Threshold
Select if the outlet should power OFF when the minimum threshold setting is reached
Minimum Threshold
Define what the minimum threshold value is
Enable Max Threshold
Select if the outlet should power OFF when the maximum threshold setting is reached
Maximum threshold
Define what the maximum threshold value is
Disconnect Holdoff Time
Number of seconds to delay power OFF when the minimum or maximum threshold setting is
reached
Reconnect Holdoff Time
Number of seconds to delay powering ON when the reading has returned to normal operating range
(only applicable if Reconnect on Normal is selected)