3
2. Connect a CAT5/5e/6 patch cable (up to 500 feet long) between the “Cat 5” port on the Sensor Converter and an “RJ45
Sensor” port on the SYSTEM. The CATx cable should be 18-24AWG in order to work at the maximum distance.
Note: Each row of RJ45 Sensor connectors (1-8 and 9-16) is rated for a combined load of 500mA. Each
ENVIROMUX-S420mA-24V uses 130mA @ 12VDC. When applying sensors, be sure that the total load on each row does
not exceed 500mA or failure of the SYSTEM may result.
Note: If you apply 3 ENVIROMUX-S420MA-24V to each row, you will not be able to use many of the remaining sensor
ports due to lack of remaining capacity.
Up to 3 ENVIROMUX-S420MA-24V can be connected to an ENVIROMUX-5D, and up to 2 can be connected to an
ENVIROMUX-2D.