CONFIGURE THE JUMPERS
Configure the jumpers on the E-AVDS-GSM for connection to either the Normally-Closed (N.C.)or Normally-Open (N.O.) relay contact
on the E-xD. In the image below, the jumpers are set for connection to the N.O. terminal.
To set the “normal” relay state to Normally-Open, apply the J2 jumper to the center and right pin, and J1 jumper to the center and left
pin. In this configuration, a relay closure will trigger an alert state, activating the dialer.
To set the “normal” relay state to Normally-Closed, apply the J2 and J1 jumpers to the center and left pins. In this configuration, a
relay open condition will trigger an alert state, activating the dialer.
NOTE: The “VOLTAGE” jumper position is not used in conjunction with the E-xD.
With the Mini SIM card installed and the jumpers properly set, re-assemble the case and attach the supplied antenna to the port on the
side of the auto dialer.
LOCATE THE IMEI NUMBER