TFTN 085-199 Installation and Operation Manual
37
Select
Burner Test
from the Test Mode screen
Select
Max Power
from the Burner Test screen
Figure 9-1 Placing the Boiler in Firing Rate Test Mode
(Continued…)
Select
Setup
from the home screen
Select
from the Setup menu
Note
: if prompted, you will need to enter the password,
“ntinet”, see
section.
Verify Burner Power goes to 100% before proceeding with
Max Power combustion calibration (see Table 9-1).
Note
: Use the Throttle Screw to adjust Max Power combustion
–
see Figure 9-2.
Note
: Verify gas line pressure to unit is within range while
operating at Max Power
–
see Table 9-1.
Note
: If the Burner Power gauge and Power Level are
flashing, it means that the Power Limiting function is
active, and the burner power will not exceed 50%.
The Power Limiting function finishes after 5min of
normal burner operation.
Upon completing Max Power calibration, select
Min
Power
from the Burner Test screen.