Installation Instructions  

 

85002 

│ Gas Valve 120Vrac VK4115 

 

 

|     3

 

Throttle Screw Adjustment

 

The gas valve Throttle Screw (see Figure 3) is used to calibrate the  CO

2

 concentration with the burner operating at or 

near  the  maximum  modulation  rate  (see  Table  2).    Turning  the  Throttle  Screw  in  (clockwise)  decreases  the  CO

concentration. Turning the Throttle Screw out (counterclockwise) increases the CO

concentration.

   

Typical adjustment 

required is 0 – 

1

/

2

 of a turn in or out from the factory setting.  

 NOTE: 

 

Calibration  of  the  Throttle  Screw  should  only  be  performed  with  the  burner  operating  at  or  near  the 
maximum modulation rate (see Table 2). 

 

Adjustments  to  the 

Throttle  Screw

  may  only  be  made  by  a  qualified  gas  technician  using  a 

calibrated  combustion  analyzer  capable  of  measuring  CO

2

  and  CO.  Adjustments  may  only  be 

performed if the gas line pressure is maintained above minimum levels throughout the duration 
of the test (see Table 1).  Failure to follow these instructions may result in serious injury or death. 
 

Offset Screw Adjustment

 

The  gas  valve  Offset  Screw  (see  Figure  3)  is  used  to  calibrate  the  CO

2

  offset  at  minimum  modulation  vs.  maximum 

modulation.    Turning  the  Offset  Screw  in  (clockwise)  increases  the  CO

concentration  at  minimum  modulation  rate.  

Turning the Offset Screw out (counterclockwise) decreases the CO

concentration at minimum modulation rate.

  

Typical 

adjustment required is 0 - 

1

/

8

th

 of a turn in or out from the factory setting. 

 NOTE: 

  

Calibration  of  the  Offset  Screw  must  only  be  performed  with  the  burner  operating  at  the  minimum 
modulation rate (see Table 2). 

 

Adjustments  to  the 

Offset  Screw

  may  only  be  made  by  a  qualified  gas  technician  using  a 

calibrated combustion analyzer capable of measuring  CO

2

 and CO, and only with the burner at 

the minimum modulation rate (see Table 2).  Attempting to set the Offset Screw while the burner 
is operating at a modulation rate other than the minimum will result in incorrect combustion and 
may lead to burner damage or excessive CO.

 

 

Gas Line Pressure Test 

The boiler gas valve is equipped with a line pressure test port; see Figure 3. Use the following procedure to measure the 
gas line pressure to the boiler to ensure it falls within the range given in Table 1: 

 

1.

 

Turn the supply of gas to the boiler off. 

 

2.

 

Open the bleed screw of the line pressure test port approximately 1-1/2 turns. This port is directly connected to the 
gas line feeding the boiler. See Figure 3. 

 

3.

 

Force  1/4

  ID  tubing  over  the  housing  of  the  line  pressure  test  port;  install  the  other  end  of  the  tubing  to  an 

appropriate line pressure test gauge or manometer.  Ensure both ends of the tubing make a tight connection. 

 

4.

 

Open the supply of gas to the boiler and check for gas leaks. 

 

5.

 

Observe  the  line  pressure  under  static  conditions  and  compare  it  to  Table  1.  The  pressure  will  be  greatest  under 
static conditions. 

 

6.

 

With all other gas appliances in the application running, operate the burner to the maximum firing rate (See Table 2) 
and compare the observed line pressure with Table 1. The pressure will be lowest during the maximum flow of gas. 

 

7.

 

Adjust the gas line pressure to ensure the parameters in Table 1 are attained under all conditions. If possible adjust 
the  line  pressure  to  the  "Nominal/Desired"  value  listed  in  Table  1,  while  the  unit  is  operating  at  the  maximum 
modulation rate, see Table 2. 

 

8.

 

Continue observing the gas line pressure until the completion of the combustion analyses, in case adjustments need 
to be made. 

 

9.

 

Complete pressure testing, and then return the bleed screw of the Line Pressure Test Port to the closed position. 

 

The  line  pressure  is  a  function  of  the  gas  supply  and  is  affected  solely  by  field  provided 
parameters  such  as  line  size  and  regulator  settings.  Under  no  circumstances  can  the  boiler  gas 
valve influence or be used to adjust the gas line pressure. 

 

Summary of Contents for 85002

Page 1: ... Replacement Instructions 1 Shut off the power and gas supply to the boiler 2 Remove the gas supply line from the gas valve 3 Remove the gas valve harness and feedback tube from the gas valve 4 Remove the screws securing the gas valve to the Venturi T25 and remove the gas valve from the boiler 5 Transfer gas line inlet adapter to the new valve Use care to ensure that the O ring gasket does not fal...

Page 2: ...adjustments record CO2 value See Throttle Screw Adjustment below 4 Set Offset Screw operate burner to the minimum modulation rate see Table 2 using the Offset Screw set the CO2 to 0 4 0 8 lower than the value obtained during the maximum modulation rate test e g if CO2 at Max 9 5 then CO2 at Min must 8 8 9 1 See Offset Screw Adjustment below Combustion Calibration is mandatory upon installation and...

Page 3: ...t the Offset Screw while the burner is operating at a modulation rate other than the minimum will result in incorrect combustion and may lead to burner damage or excessive CO Gas Line Pressure Test The boiler gas valve is equipped with a line pressure test port see Figure 3 Use the following procedure to measure the gas line pressure to the boiler to ensure it falls within the range given in Table...

Page 4: ...urner operating at maximum modulation rate when tested at minimum modulation rate the CO2 must be 0 4 0 8 lower than CO2 at maximum modulation rate Table 2 Minimum and Maximum Modulation Rates Model Min Modulation Rate RPM Max Modulation Rate RPM Tx200 1000 7300 Tx200C 1100 6650 Note Use Installer Menu setting 2 15 to force the burner to operate at the max 2 15 3 and min 2 15 1 modulation rates se...

Reviews: