TECHNICAL SPECIFICATIONS
Humidity measurement
Measurement range:
•
Configurable: Between 0 % RH and 100 % RH (no condensing);
•
Configurable: Between -90 °C at 100 °C in dew point.
Response time (1/e (63 %)):
< 4 seconds
@25 °C (with air moving at 1 m/s and polyamide tip)
Temperature
measurement
Measuring Range:
•
-40 °C to 100 °C for DM models;
•
-40 °C to 60 °C for WM models.
Response time (1/e (63 %)):
< 5 seconds
@25 °C (with air moving at 1 m/s and polyamide tip).
Accuracy
•
Temperature: ± 0.4 °C (0 °C to 60 °C);
•
Relative Humidity: See image below.
•
Degradation of relative humidity reading over time: < 0.5 % RH/a | < 0.05 K/a
Power supply
•
Power supply via PWR terminals: 12 Vdc to 30 Vdc;
•
Power supply via USB cable: 4.75 Vdc to 5.25 Vdc;
Internal protection against power supply voltage reverse polarity.
Maximum power supply
current
< 70 mA ±10 % @ 24 Vdc
0vt1
/
0vt2
Output
They may be configured independently to operate with signals 0-10 V or 4-20 mA.
•
0-10 V
o
Maximum current: 2 mA;
o
Resolution: 0.003 V.
•
4-20 mA
o
500 R maximum load;
o
Resolution: 0.006 mA.
Alm1
Alarm
alm2
Alarm
•
Channel N 30 V / 200 mA type output;
•
Protection against current > 200 mA;
•
Current protection reset time: 5 seconds.
Protection rating
•
Electronic module housing: IP65;
•
Sensor capsule: IP40 or IP20, according to the models: sintered PTFE (with device) or polyamide (optional).
Housing
ABS+PC
NXperience
Windows 10, 8 / 8.1, 7, Vista and XP (32 and 64 bits) configurator software.
Menus in Portuguese, Spanish, French and English.
Certifications
CE Mark
This is a Class A product. In a domestic environment, this product may cause radio interference in which case the
user may be required to take adequate measures.
Table 67
– Technical specifications