Indicator N1500  

NOVUS AUTOMATION 

5/7 

Al1t1 
Al1t2 
Al2t1 
Al2t2 
Al3t1 
Al3t2 
Al4t1 
Al4t2

 

Alarm Timer 
The user can set delayed, momentary or sequential alarms 

by configuring times T1 and T2 according to Table 3
To disable this function just set zero for T1 and T2. 

FUNCTION LEVEL 

f.fvnc 

  KEY FUNCTION –  Defines functions for the 

 

key. The available options are: 

oFF

 -  Key not used. 

Hold

 -  Hold PV 

RSt

 -  Resets Peak and Valley (MAX and values)  

P.koL

 -  Peak Hold 

Dig.in

 

Digital Input Function – Defines the function for the digital 

input. Refer to item 5.2. Options are: 

oFF

 - 

kold

 - 

rSt

 - 

PkoLd

  

filtr

 

Input Digital Filter - Adjustable from 0 to 60, this is used 

to reduce instability of the measured value. 0 means the 

filter is off and 60 means maximum filtering. The higher the 

filter value, the slower the response. 

ofset

 

Display Offset - This a value which is added to the PV to 

offset any measurement  deviation or sensor error. The 

offset is shown in the programmed engineering unit. For °F 

measurements the null reference is at 32 °F. 

bavd

 

Baud Rate -  Serial digital communication speed in bps

Programmable:  
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115.2. (no 

parity) 1.2P, 2.4P, 4.8P, 9.6P, 19.2P, 38.4P, 57.6P and 

115.2P (with EVEN parity). 

Adres

 

Communication Address  -  A number that identifies the 

instrument in a multidrop network. 

 

CONFIGURATION LEVEL 

In.typ

 

 

Input Type - Selects the input signal or sensor type to be 

connected to the PV terminals. Refer to Table 1 for options. 
Changing the input type causes all other parameters 

related to PV and alarms to be changed as well, therefore, 

this parameter shall be the first to be set. 

Dp.pos

 

Decimal  Point Position  -  Defines the decimal point 

position in the displayed value. It is displayed when linear 

input types 0-50  mV, 4-20 mA, 0-5 V or 0-10 V are 

selected at the “

in.tYP

” prompt. 

Vnit

 

Temperature Unit - Selects °C or °F indication. This prompt 

is not shown for input types 0-50 mV, 4-20 mA, 0-5 V or 0-10 

V are selected at the “

in.tYP

” prompt. 

s.root

 

Square Root - This prompt is only shown when input types 

0-50 mV, 4-20 mA and 0-5 V are selected at the “

in.tYP

” 

prompt. 
Set “

YES

” and the square root will be applied to the 

measured value within the limits programmed in “

in.LoL

” 

and “

in.kiL

”. 

The display will show the low limit (

in.LoL

) value should 

the input signal be below 1 % of the range. 

Scale 

Scale - Defines the indication range for linear inputs (0-50 

mV, -20 mA, 0-5 V and 0-10 V). 

0

  Configurable indication from – 31000 to + 31000. 

1

  Configurable indication from 0 to + 60000. 

2

  Configurable indication from 0 to +120000. Only even 

values will be displayed (resolution is not improved). 

The selected scale affects values of PV, alarm setpoints 

and Offset. 

In.lol

 

Input Low Limit - Sets the low limit for input type 0-50 mV, 

4-20 mA, 0-5 V or 0-10 V. When the PV Retransmission 

is used this limit defines the corresponding 4 mA (or 0 mA) 

in relation to the input value. 

In.kil

 

Input High Limit - Sets the high limit for input type 0-50 

mV, 4-20 mA, 0-5 V or 0-10 V. When the PV 

Retransmission  is used this limit defines the 

corresponding 20 mA in relation to the input value. 

Ou.lol

 

Low Limit for Analog Retransmission  –  Defines the PV 

value that results in a 4 mA (or 0 mA) analog output current. 

Ou.kil 

High Limit for Analog Retransmission – Defines the PV 

value that results in a 20 mA analog output current. 

Ovt.ty

 

Analog Output Type - Selects the analog output type to 

either 0- 20 mA or 4-20 mA. 

Ovt.er

 

4-20 mA Output behavior in case of failures – Defines the 

output as 4-20 mA when there is an error in the indication. 

Do

 – Applies a value < 4 mA;  

UP

 – Applies a value > 20 mA 

CUSTOMIZED LINEARIZATION LEVEL 

Inp.01 

Inp.30

 

Defines the initial  and  end  analog input values for each 

custom segment line. The values  must be entered in the 

input signal unit: 
0-50 mV, 4-20 mA or 0-5 V. For 0-10 V select 0-5 V. 

Ovt.01 

ovt.30

 

Defines the corresponding indication that each custom 

segment is to show. Values are expressed in the desired 

indication unit (within the Indication Lower and Upper 

Limits). 

Table 5 shows the sequence of levels and parameters presented in the indicator display. There are parameters that must be defined for each alarm 

available.

 

WORK LEVEL 

ALARM LEVEL 

FUNCTION LEVEL  CONFIGURATION LEVEL  CUSTOMIZED LINEARIZATION LEVEL  CALIBRATION LEVEL 

8.8.8.8.8. 

*

 Fv.al1 

f.fvn( 

In.typ 

Inp.01 

-

inp.30 

In.lo( 

Al.ref 

*

 Df.al1 

Dig.in 

Dp.pos 

OVt.01 

ovt.30 

In.ki( 

*

 Sp.al1 

*

 Ky.al1 

Filtr 

Vnit 

 

Ov.lo( 

 

*

 Bl.al1 

Ofset 

Sroot 

 

Ov.ki( 

 

*

 Al.1t1 

Bavd 

Scale 

 

(j lo 

 

*

 Al.1t2 

adres 

In.lol 

 

k.type 

 

 

 

In.kil 

 

 

 

 

 

ov.lol 

 

 

 

 

 

Ov.kil 

 

 

 

 

 

OVT.TY 

 

 

 

 

 

OVT.er 

 

 

Table 5 - Sequence of levels and parameters displayed by the indicator

* Parameters that require definition for each available alarm. 

Summary of Contents for N1500

Page 1: ...ommunication optional 3rd and 4th alarm relays optional PROCESS VARIABLE INPUT PV The process variable PV input type is configured through the frontal keypad according to the codes shown in Table 1 re...

Page 2: ...rm output to be delayed or to deliver a single pulse or a train of pulses The delay the pulse width and the period are defined by the user Table 3 shows these advanced functions Times T1 and T2 can be...

Page 3: ...uld be suitable for this purpose and should not be shared In controlling and monitoring applications possible consequences of any system failure must be considered in advance The internal alarm relay...

Page 4: ...a level press the and keys simultaneously for 3 seconds while in the level To unlock the level press and for 3 seconds The display will briefly flash confirming that the level was successfully locked...

Page 5: ...ay will show the low limit in LoL value should the input signal be below 1 of the range Scale Scale Defines the indication range for linear inputs 0 50 mV 20 mA 0 5 V and 0 10 V 0 Configurable indicat...

Page 6: ...en The device must be withdrawn from the case and immediately placed in an anti static wrap protected from heat and humidity INPUT CALIBRATION All inputs are factory calibrated and recalibration shoul...

Page 7: ...imum RH 80 up to 30 C For temperatures above 30 C decrease 3 per C Panel protection IP65 for indoor use Installation category II pollution degree 2 altitude 2000 m INPUT Keyboard selection of input ty...